MECHANICAL PRELIMINARY DESIGN REPORT STADIUM 1.给排水设计 饮用水和污水 Design Water and sewage water .设计基础 - 甲方提供的设计任务书和市政管网综合图 - 建筑专业提供的条件图 - 国家现行的设计规范及有关规定设计简章 .Design bases Design Brief and Municipal integrated network drawing offered by the client. Condition drawings from architectural discipline. Current national design codes and related stipulations 2. 给水系统 通过一根DN200的进水管将水引入.水表安装在进水管上,离红线1米处.供水管在红线内连成环路管网,并接到供应楼的消防水池和给排水水池.由环路管网向必需的室外消火栓和绿化带的喷淋器供水. 2. Water supply system For water supply of this project, DN200 water intake pipes are led in. Water meters are installed on the intake pipes m away from the red line. The water supply pipes are connected into loop networks in the red line and then led to the fire pool and sanitary water pool in the supply buildings respectively. Necessary number of outdoor hydrants and sprinklers for green area will be provided on the loop networks. 设计范围 包括红线内的饮用水,污水,雨水,建筑消防. Design scope Design scope of this project includes water, sewage water, rainwater, fire-protection in the building, and water and sewage water within the red line. 给排水水池与消防水池分开,容量为100m3 .体操馆供水管埋地敷设. Sanitary water pool is separated from fire water pool, volume of sanitary water pool is 100m3. Water supply pipes for the stadium will be laid in the earth. 3.用水量标准 - 体育馆: 15升/顾客·日 K= - 宾馆: 150升/人·日 K= - 餐厅: 50升/顾客·日 K= - 工作人员: 25升/人·日 K= - 地面冲洗用水: 3升/m2日 - 冷却塔补水量:按用水量的2%计 - 未预见水量: 按日用水量20%计 - 消防用水: 消火栓:室内40升/秒,室外30升/秒,火灾延续时间为3小时; 自动喷洒按22升/秒,火灾延续时间为1小时 卷帘水幕用水升/秒·米,火灾延续时间为3小时; Water consumption standard - Stadium: 15L/visitor·day K= - Hotel: 150L/visitor·day K= - Restaurant: 50L/customer·day K= - Staff 25L/person·day K= - Floor cleaning: 3L/m2·day Make-up water for cooling tower: 2% of the actual cold water consumption. Unforeseen water consumption: 20% of the daily water consumption. Water for fire protection Hydrant: 40L/s indoor, 30L/s outdoor, fire duration time is 3h; Sprinkler: 22L/s, fire duration time is 1h; Drencher for rolling shutter: ·m, fire duration time is 3h; 在适当的位置设置饮用水机,在主进口为残障人设置两个饮用水机.为此饮用水系统安装循环泵.机房 设在地下室的水除了机房.当饮用水机不被使用时,应排空,以免水质腐败. 在客房和餐厅内设置电热水器,同时亦为热水供应设置循环泵. 在更衣间旁设置电热水器,为淋浴和洗盥供应热水. 为楼板清洁安装一定数量的水龙头. Some suitable places are supplied with portable water drinking units, two drinking units for disable people are provided at main entrances, for this portable water system, circulating pumps are adopted, the equipment room is located in water treatment center in the basement. When there is no use, portable water will be drained completely to avoid deterioration. Electric water heaters are installed in guest rooms and restaurant, also hot water circulating pumps will be provided for supplying hot water. Electric water heaters are installed near the changing and clothing rooms for supplying hot water for shower and washing. Certain number of water taps are installed for floor-cleaning. 4.用水量 最大日用水量:日 最大时用水量:220m3/时 Water consumption demand Maximum daily water consumption: Maximum hourly water consumption: 220m3/hour 却循环系统 冷却水循环系统采用机械循环系统.总冷却水用量为460m3/h.在供应楼顶设置三台超低噪音冷却塔(230 m3/h, 2x 115 m3/h).进水温度37Co,出水温度32Co .补充水量 9,6 m3/h.补充水由市政供水网直接提供. Cooling water circulation system There are cooling water circulation system in this project, cooling water for the refrigerators adopts mechanical circulation system. Total water consumption of cooling towers is 460m3/h. On roof of the supply building there are 3 ultra-low noise cooling towers (230 m3/h, 2x 115 m3/h), inlet temperature of 37Co, outlet temperature of 32Co, with make-up water of 9,6 m3/h. Make-up water of the cooling towers will be supplied directly by the municipal network. 在消防泵房内有消火栓泵(一个运行,一个备用),喷淋泵(一个运行,一个备用),卷帘雨淋泵(一个运行,一个备用).用于地下车库的泡沫喷淋设备,如报警阀,泡沫压缩罐,化学药剂泵安装在消防设备中心. 消防水箱和消防稳压装置分别安装在车库的四面墙. In the fire water pump room, there are hydrant pumps (one operation, one standby), sprinkler pumps (one operation, one standby) and rolling shutter drencher pumps (one operation, one standby). Fire equipment, which are used for the foam sprinkler system in underground garage, such as fire alarm valves, foam concentrated tank and chemical dosing pump, etc. are provided in fire equipment centers. Four fire water tanks and fire protection stabilized pressure devices are respectively located at four sides next to the garages. 消防用水 消火栓:室内按40升/秒,室外按30升/秒,火灾延续时间按3个小时计 自动喷洒按22升/秒,火灾延续时间按1小时计 卷帘水幕用水量 升/秒·米,火灾延续时间按3个小时计 消火栓:室内,室外用水量皆为756m3; 自动喷洒用水量为 m3; 卷帘水幕用水量为 270m3; 一次火灾用水量为; Water for fire protection Water consumption standard for fire protection Hydrant: 40L/s indoor, 30L/s outdoor, fire duration is 3h Sprinkler: 22L/s, fire duration is 1h Drencher for rolling shutter: ·m, fire duration is 3h Water consumption for fire protection Hydrant: indoor and outdoor water consumptions are 756m3 respectively Sprinkler: m3 Drencher for rolling shutter: 270m3 Water consumption for one fire: m3 消火栓的布置 在整个建筑物内沿墙,沿柱,沿走廊,风塔上及楼梯附近设有必要数量的室内消火栓,消火栓间距小于30米.消火栓管网水平,竖向皆成环状布置,消火栓箱内配有DN65消火栓一支,25米衬胶水龙带一条,φ19毫米喷咀水枪一支,并配消防卷盘(DN25消火栓一支,30米胶管,φ9毫米喷咀水枪一支)且设有可直接启动消火栓泵的按钮;在室内消火栓箱下设有磷酸铵盐手提式灭火器箱.室内消火栓系统在室外设有三组水泵接合器. Hydrant arrangement Necessary number of hydrants are installed indoors along the wall, columns, corridors, and staircases, at intervals of less than 30m. Hydrant networks are connected as a loop both horizontally and vertically. Inside each hydrant box, a DN65 hydrant, a 25m long rubber lined hose, a water nozzle of φ19mm, hose reel (a DN25 hydrant, a 30m long rubber lined hose and a water nozzle ofφ9mm), and a direct starting button for the hydrant pump are provided. Under each indoor hydrant box, a portable ammonium phosphate powder extinguisher box is installed. There are three sets of pump adopters being installed outdoors for the indoor hydrant system. 消防系统 防水泵房及消防水池 供水管DN200在红线内连成环路管网,管网上安装 一定数量的消火栓.两根DN200供水管分别引入供应楼内两个消防泵房内的消防水池.消防水池总容量不应小于4000m3, 每个为. Fire protection system Water pump room and water pool for fire protection The lead-in pipes (DN200) are connected as a loop inside the red line, on the loop, certain number of hydrants are water supply pipes (DN200) are led into the fire water pools at each fire water pump room in supplybuilding. In consideration of the importance of the project, the volume of the fire water pools should be not less than 4000m3, each is . 自动喷淋系统 自动喷淋系统安装在全建筑范围,除了室外和高于10 米的房间.喷淋泵安装在地下的消防泵房内.报警阀设置在地下的消防泵房内和中间的消防设备中心内,水流显示器设在每个防火分区内. Sprinkler system Sprinkler systems will be provided inside the whole building except outside areas and roomshigher than 10m, with sprinkler pumps installed in the underground fire water pump rooms. Alarming valves installed in underground fire water pump rooms and four fire equipment centers in the middle, water flow indicators are installed by fire compartments. 除了安装一个封闭喷淋系统,将为地下车库设置一个泡沫喷淋系统.餐厅内安装93oC启动的自动喷淋头,但在其它房间,仅安装93oC启动的普通和快速反应自动喷淋头.三组泵接合器安装在室外. Besides an enclosed sprinkler system, a foam sprinkler system composed of a proportioning mixer and a foam concentrated tank is provided for the underground garage. Sprinkler actuated at 93oC are provided in the restaurants, but in other rooms, only ordinary sprinklers and fast response sprinklers actuated at 68oC are provided. Three sets of pump adaptors for this system will be installed outdoors. 排水系统 为排水系统设置污水主立管和特别垂直排气管.排气管与污水管在每层连接,污水排出体操馆.餐厅的污水首先在油脂分离池中处理,然后排入室外排水网.给排水污水将被在化粪池收集和处理,然后排入市政排水管网.化粪池在输送区旁.最大天排水量为870m3/天. 9. Drainage system Main vertical sewage pipes and special vertical vent pipes are provided for the drainage system. The vent pipes are connected with sewage pipe at each floor; sewage water is drained out of stadium. Sewage water in the restaurants and garage are treated in the grease and oil separation tank, and then discharged into the outdoor drainage networks. Sanitary sewage water is collected and treated in the septic tank, then drained into the municipal drainage. The septic tanks are located besides the deliverycircle. Maximum daily drainage amount is 870m3/day. 卷帘水幕系统 地下车库设置有卷帘水幕系统.水幕泵安装在消防水泵房内,采用开式雨淋头,电动或手动控制.十组泵接合器安装在室外 Drencher system for rolling shutters Rolling shutter protected by drenchers are provided for the underground garage, the drencher pumps are installed in the fire water pump rooms, open drencher heads are selected, and are controlled both by electrically and manually. Ten pump adapters will be installed outdoors for this system. 地下室内污水设有污水坑,废水设有废水坑,生活污水,废水经潜污泵提升排至室外排水管网,潜污泵的启停皆由磁性浮球控制器的控制. 地下汽车库废水设有废水坑,废水经潜污泵提升排至室外,经隔油池处理后排入室外雨水管网. There are cesspits for sewage water and wastewater pits for wastewater in the basement, the sewage and wastewater is sucked up and drained to the outdoor drainage networks by submerged sewage pumps. Operation of the pumps is controlled by the magnetic floating ball controllers. Wastewater pits are provided for the underground garage, wastewater is sucked up and drained to outdoor oil separation tank by submerged sewage pumps, after treated, wastewater is drained to the outdoors rainwater networks. 在柴油发电机房,变配电房和通讯设备机房设低压二氧化碳气体灭火系统. Low pressure CO2 extinguisher systems are provided in diesel generator rooms, transformer substations and telecommunication equipment rooms. 在本建筑内按"建筑灭火器配置设计规范"在每个消火栓箱下设手提式灭火器箱,箱内设有必要数量的磷酸铵盐手提式灭火器. According to the Code for Design of Extinguisher Disposition in Buildings, portable fire extinguisher box, in which there are necessary number of portable ammonium phosphate powder extinguishers, will be installed under every hydrant box. 在每个消防电梯井底旁设有消防排水坑,废水经潜污泵提升排至室外. Fire water drain pit is provided at side of bottom of each fire elevator well, waste water will be sucked up and drained out by the pumps. 雨水系统 雨水排水屋顶采用压力流排水. 雨水设计重现期按P=10年计算,降雨历时为5分钟,暴雨强度公式按Q=(1+)/(t+)计算. 沿柱在屋面设置雨水沟.雨水通过雨水沟收集,然后进入雨水头和下排管,然后到室外雨水观察井. 10. Rainwater system Pressurized drainage system is adopted for roof rainwater drainage system. Here, return period P=10 years, rainfall duration is 5 minutes, stormwater amount is calculated by the following formula: Q=(1+)/(t+) Rainwater gutters are provided on roof along columns, skylight. Rainwater is collected in the gutter, then to rainwater heads and downpipes, and to the outdoors rainwater inspection wells. 11.管材 - 生活给水管,冷却塔补水管采用铜管,氩弧焊接. - 直饮水管采用不锈管. - 消火栓管,冷却循环管,水幕管,水泵吸水管采用焊接钢管,焊接. - 自动喷洒水管,雨淋水管采用热镀锌钢管,丝扣连接或卡压连接. -二氧化碳管采用无缝钢管焊接. - 地下车库泡沫喷淋水管采用不锈钢管,卡压连接. Pipe material Copper pipes connected by argon arc welding are adopted for the sanitary water pipes, make-up water pipes for cooling towers. Stainless stell pipes are adopted for portable water pipes. Welded steel pipes connected by welding are selected for hydrant pipes, cooling circulating pipes, drencher pipes, pump suction pipes. Hot-galvanized steel pipes connected by threads or compression-seizing are selected for sprinkler and deluge sprinler pipes. Seamless steel pipes connected by welding are selected for CO2 pipes. Stainless steel pipes connected by pressed clamp is selected for the pipes of foam sprinklers in the underground garage. 当雨水两超出雨水沟设计量时,雨水可沿屋檐自由排放.雨水被收集,然后排入市政集水池. When the amount of rainwater is more than the design value of the gutters, water is discharged naturally along the eaves. Rainwater is collected, and then drained to the municipal catch basins. 围绕体育馆的循环池将用于喷洒运动场和作为室外绿化带的储水池. 此池将作为一个循环过滤设施,可容水约 m . 喷洒压力设备和其它必须的过滤设备安装在供应楼里. The circular senic pool surround stadium will be used for spraying sportsfield and as reservoir for outdoor greening. The pool will be used as a circular filtering facility and will be adopted with a water volume of about m . The spray water pressurizing equipment as well as further necessary filtering equipment will be adopted in the supply building. 制冷 Cooling 冷源: 空调冷负荷(估算): 本工程建筑面积共平方米,包括观众区,休息室,更衣室,小会议室,餐厅,办公室和其它附属房.空调设计日峰值冷负荷为,设计日总冷负荷为3 kW. Refrigerating source Cooling load of air conditioning system Total floor area for this building is 50,000sqm, which includes spectator areas, lounges, Clothing and changing rooms small meeting rooms, restaurant, office and other auxiliary rooms. Designed dayly peak cooling load is 2,4MW, designed total dayly cooling load is 3kW. 每台1200kW制冷机配一台 流量为206m3/h离心泵.各配一台备用泵 一次泵采用压差旁路控制. 通过埋地敷管,向游泳体操馆供应冷冻水. A centrifugal pump with a flow rate of 103m3/h is provided for each 1200kW chiller. One operation pump with a standby corresponds to one chiller. Pressure difference branch control is adopted for primary pump Via earth laid pipes from supply building to gymnasium chilled water supply will be deliverded. 冷源的选择: 根据建筑的实际情况,3台制冷机将安装在供应楼内的冷冻机房.设计容量为4800kW. 为了实现能量的效率化使用,设计方案为,1台制冷机的出力为总设计容量的50%.而另2 台.每台出力为总设计容量的25%. 冷冻水系统的主要设备包括3台电动制冷机,一级冷冻泵,二级冷冻泵,自动控制阀等等.冷冻水的供/回水温度为-7/ 12°C. Selection of refrigerating source According to the real condition of the building, 3 chillers are located in the refrigerating plant rooms in the supply building, designed capacity is 2400kW. For actuing in an energy efficient way one chiller about 50% of total capacity ( kW) and two chillers with 25% of total (600 kW each)capacity each are adopted. Main equipment of chilled water system includes 3 electrical chiller, primary cool water pump, secondary chilled water pump and automatic controlled valve, etc. supply/return temperature of the chiller is-7/ 12°C. 二次泵系统:根据使用功能,各制冷机房又分成不同的循环支路. 二次泵采用变频调速控制.根据负荷侧供回水管的压差,控制水泵的转速. 二次泵循环支路的管道采用异程式. Secondary pump system: Each refrigerating plant room is subdivided into different circulation branch loops according to use functions. Variable-frequency speed-regulating control is adopted for secondary pumps. The rotating speed of a water pump is controlled according to the pressure difference between water supply and return pipes. Direct return system is adopted for the pipes of circulating branch of secondary pumps 空调冷冻水系统 由于本工程占地面积大,功能复杂,有连续使用,也有间歇使用,为了达到运行灵活,节能的目的,空调冷冻水系统采用两管制二次泵系统. Chilled water system Due to the large occupied area of this project, the complicated functions and the combination of continuous utilization and intermittent utilization, in order to accomplish the purpose of flexible operation and energy saving, the chilled water system is of two-pipe secondary pump system. 管材: 水管采用焊接钢管及无缝钢管. 本工程的风管除土建风道外,均采用镀锌铁皮咬口制作.每节风管之间用法兰连接. Pipe and duct materials The water pipes adopt welded steel pipes and seamless steel pipes. Air ducts for this project are made of galvanized sheet steel by seaming except ducts by civil construction. Air ducts are connected together by flanges. 一次泵系统: 供应楼冷冻机房 2400kW制冷机配一台离心泵, 流量为412m3/h.配一台备用泵. Primary pump system: Chiller room supply building A centrifugal pump with a flow rate of 412m3/h is provided for 1200kW chiller. One operation pump with a standby corresponds to one chiller. 保温材料: 空调供,回水管,冷凝水管采用酚醛管壳保温. 空调送,回风管以及处理后的新风管采用外贴铝箔的离心玻璃棉板保温. - 管道穿防火墙的空隙处采用岩棉材料等非燃材料填充. Thermal materials phenolic pipes are adopted for thermal insulation of water supply and return pipes for air conditioning, as well as air-conditioning condensate pipes. Aluminum foil faced glass fiber boards are adopted for thermal insulation of air-conditioning air supply and return ducts as well as fresh air ducts after chillers. Non-flammable material will be selected to fill the interspace in the fire protection wall where the ducts go through. 消声与隔振: 冷水机组,水泵等设备采用减振台座,弹簧减振器或橡胶减振垫减振降噪. 在空调机组,新风机组,通风机的进出口采用涂胶帆布软管连接. - 水泵进出水管上采用可曲挠橡胶接头,使设备振动与配管隔离. Noise reduction and vibration isolation Shock absorption bases, spring shock absorbers on rubber shock absorption pads are adopted for equipment, such as water chiller units, pumps, etc to reduce vibration and lower noise. Flexible rubber-coated canvas hoses are adopted far connections of inlets and outlets of air-conditioning units, fresh air handling units and ventilators. Flexible rubber couplings are adopted for the water intake and delivery pipes of the pumps to isolate equipment vibration from their pipes. 空调和通风系统 Air Conditioning and Ventilation Systems 方案设计范围 Scope of schematic design 空调设计 Air Conditioning Design 在体育馆内,一些区域设置空调系统.这些区域划分为: 西侧地下二层的贵宾休息室 东侧地下二层酒店门廊 地下一层的输送区,技术机房,运动员更衣间,医务服务,热身区,裁判区,健身中心,酒店大堂,会议室,厨房,特许区和贵宾大堂混合区. 首层的酒店大堂,酒店区,贵宾门廊,急救 In the stadium, in some ranges air conditioning systems are used. These ranges subdivide themselves as follows: VIP – Lobby in West of levelel -2 Hotel lobby in the east of level –2 Delivary Circle, technical Plantrooms, Changingrooms for the athletes, Medical Service and warm up area, Judges Area, Fitness Center, Hotel Lobby, Conferenz, Kitchen and Concession, Vip lobby- Mixed Zone in level -1 Hotel lobby, Hotel area, Vip lobby, Vip Area, First aid in 0
随着我国现代建筑技术的不断发展,人们对于建筑给排水工程方面也提出了越来越高的的要求。下文是我为大家整理的关于建筑给排水工程论文的范文,欢迎大家阅读参考!
浅谈高层建筑给排水工程设计
摘要:对高层建筑给水系统设计,排水系统设计、室内消防和热水系统设计进行了详细介绍,总结出目前高层建筑给排水存在的问题,并探讨了给排水节水措施,以确保水资源的合理利用。
关键词:建筑给排水;高层建筑;设计;节水措施
1、高层建筑给排水工程设计方法
高层建筑给水排水工程与一般多层建筑和低层建筑给水排水工程相比,基本的理论和计算方法是一致的,但因高层建筑层数多,高度大,结构复杂。近年来建筑给水工程设计方法得到改进。
例:给一个高层建筑为15层的楼房设计给排水:
住宅楼为框架结构,共15层,层高,室外给水管网位于建筑物的北侧,距离外墙为10m,接管点埋深,管径400mm,管材为球墨给水铸铁管,常年提供的水头;室内粪便污水需要经过化粪池处理方可排入市政管网,室外排水管网位于建筑物的南侧,埋深2m,管径600mm,管材为聚乙烯双壁波纹排水塑料管。
设计参数
生活用水定额:qd=150L/(人.d);最大小时生活用水量:Qh=;最高日用水量:Qd=;小时变化系数:kh=;每户人口:m=人;共90户;室内消防用水量:10L/s;消防水箱水量为火灾前10min的水量6m?;贮水池内的消防水量:按火灾延续2h的水量计;雨水重现期:2年。
设计内容
给水系统设计
管道采用钢塑复合管(内衬塑外镀锌)螺纹连接,进行干管安装、立管安装、支管安装,管道安装完毕需进行水压试验,压力设在,并对安装好的管道做好防腐和保温工作,冲洗管道对其进行管道通水试验。
根据《建筑给排水设计手册》上卫生器具的最大静水压力不得超过,因此高层建筑给水系统必须分区。设计任务书给定了市政给水管网提供常年的水压为。根据给水最小所需压力估算方法:第1层,第2层,2层以上增加1层,压力需增加。得的压力能直接供到第6层还多。所以1层~6层为一个区,上面7层~15层为一个区,总共就两个区。1层~6层用市政管网直接供水,其中底层和2层~6层单独设立管。
考虑到此设计对象是15层的高层建筑。市政管网提供的压力不能全部直接供水,所以必须对生活用水进行提升或加压。高层建筑设计一般都使用高位水箱供水,供水压力比较稳定,此设计也使用高位水箱;又因此设计面向高层民用住宅楼,通过查看平面图纸,根据建筑物的布置情况和楼层的承载力情况及水箱本身占用大量的建筑面积,即在楼层中间没有建筑面积可允许安置水箱,串联供水不可实现,因此高区的供水应在地面用泵抽升到高区水箱。
方案(一)与方案(二)相比管材使用量、工程投资相对较少,但它对减压阀的质量要求相对较高,一旦减压阀受损或使用性能降低,低区的静水压力会迅速增加,影响卫生器具的使用。方案(二)采用低区市政管网直接供水,消除了通过依赖减压阀降低静水压力来减少低区供水的现象。基于工程质量和供水水质及水压的可靠性,最终选择方案(二)
排水系统设计
室内排水系统为污水、废水合流系统,地上部分直接排出室外,地下部分分段设置集水坑把地下室污水、废水汇集于坑内,利用潜水泵由集水坑自动控制将其提升至室外。为了保护存水弯水封性能,保持排水系统内的空气压力与大气压取得平衡,使排水管内排水畅通,向排水管内通入新鲜的空气,保持管内的换气,防范因室外管道系统积聚起来的有害气体而伤害到养护人员、引发火灾和腐蚀管道等隐患,还应减少排水系统的噪声,在排水系统中设置通气管。
室内消防工程
室内消火栓给水系统有:分区、不分区两种方式。消火栓的静水压力超过时就需要分区供水,而本设计是15层的小高层,高度不超过50m,静水压力小于,可以不分区。同时本设计的建筑是15层小高层民用住宅楼,造成火灾的隐患少,人员疏散也快,扑救难度不大,高压消防给水无须设置常年的。设置专用的消防泵,从贮水池内抽取消防水,可用生活给水箱在火灾发生初期10min提前给水,并设置止回阀,既消除了消防水箱对楼层负荷,又可减少工程投资。此设计是15层小高层,层高,总楼高不超过45m,根据建筑给排水设计手册!规定消防栓的最大静水压力不超过,此设计无须分区消防供水,可利用消防泵直接供水满足条件。
室内热水工程
应根据建筑物的用途、热源的供给情况、热水用量和卫生器具的布置情况进行技术和经济比较来确定何种热水供应方式。热水供水方式有如下几类。按供应范围不同有:集中供热、局部供热、区域供热。
2、目前建筑给排水存在的问题
控制超压出流产生的水量浪费
生活给水系统按规定竖向分区后仍然存在着部分卫生器具配水点水压偏大的问题,而这是常常被忽视的。卫生器具的额定流量少于单位时间内的出水量,影响给水系统正常分配水的流量。如不采取减压节流措施,将造成水资源浪费、水压过高、漏水量增加等弊病,同时易产生水击、噪声和振动,致使管件损坏和破裂。这些水量的浪费不容忽视。
管道和阀门的损坏
我们可看到的路边给水管道在管子接缝处及法兰、阀门连接处向外冒水,而我们看不见的地下更不知有多少漏水处。管道受损及腐蚀,阀门不严等问题导致大量水流失。
热水系统浪费水量巨大
建筑热水供应已成为建筑给水的重要部分,由于设计不当,其浪费已非常严重,造成一定损失。所以给水系统供水应保证冷热水压力均衡,采用循环系统以确保每户开龙头就有热水,降低水量浪费。
3、我国建筑给排水节水措施
提高用水效率
1)严格执行生活用水量定额标准,饮用水、生活用水、景观用水、绿化用水按各个水质要求分别供给。
2)采用节水系统,如节水的卫生器具,利用限制卫生器具的流出水头、红外线感应龙头和便器等。
3)选择一个可再生能源,如风能、太阳能、水能、海洋能、地热能、生物能等非化石能源用于建筑的热水供应。对于不同的场合采用不同的热源形式。
雨水的利用
利用雨水收集系统再循环得到符合标准的水质进行绿化浇灌,处理后的雨水还可用于冲洗厕所,这不仅可减少用水量还可减轻污染。提高地基的保水能力,合理规划雨水流经途径,引入雨水沉淀池再利用。
污水排放和二次利用
建筑中水系统是典型的资源可持续利用装置,将建筑物产生的污水、废水加以收集并对其处理,在节省资源和保护环境的基础上对生活污水和废水的重复利用。
节水指标
节水指标有三类:
1)雨洪水利用率:常年降雨量除以使用或收集量;
2)水使用率:正常使用量除以使用量;
3)循环量:一次性用量乘以循环次数。
4、结语
在给排水设计时,我们应正确合理的选择系统和方案,以达到节水节能的目的,确保水资源的合理利用。
参考文献:
[1]孙志魁.我国绿色建筑给排水节能新技术的应用新探.中国新技术新产品,2012(1):45.
[2]杨天峰,张旺.低碳经济下建筑给排水的节能问题研究.科技创业月刊,2010,23(9):161-162.
[3]赵培林.浅议绿色建筑住宅的节水设计.机电产品开发与创新,2009,22(3):40-41.
[4]李倩.绿色建筑给排水设计的节水途径探析.企业导报,2012(1):273.
浅析建筑工程给排水施工技术
摘要:本文作者结合实际工作经验,对建筑工程的给排水施工技术进行了分析,提出了自己的见解。
关键词:建筑工程;给排水;施工技术
随着我国现代建筑技术的不断发展,人们对于建筑给排水工程方面也提出了越来越高的的要求。在设计和施工时要不断积累经验,深入分析各种常见问题,促进给排水施工技术的发展。
1 建筑给水方面的管道施工
给水管道材料的种类和选用
现在在新型建筑中用的较多的给水管材主要包括:聚丙烯类、聚乙烯类、聚丁烯类、工程塑料类,以及还有一些复合管类,例如:钢塑管、铝塑管、铜塑复合管等。虽然可供选择的材料有许多种,但在每一个具体施工工程中也必须根据实际情况进行选择。而且在管材的选用上还受到许多因素的影响,必须对国家政策、施工标准、地区特点、工程性质以及施工标准等因素进行综合考虑,选择最优管材。其中还要特别注意的是,管道的使用位置以及其使用方法是在管材选用时需要着重考虑的,还有就是管件与连接也是选取管材时容易忽视的一个关键的问题。
给水管道的施工
在对给水管做热熔连接时,必须要掌握好加热的时间和连接将要插入的深度。如果加热时间过长就使水管融化,如果加热时间过短也不能更好连接;如果插的过深,就会造成管道断面减少;如果插的过浅也会使降低接口处强度。所以,加热时的温度、加热时间和接缝压力是影响热熔连接质量的三个关键因素。
2 建筑排水管道常见问题的原因分析
排水管道方面经常出现的问题是漏水、堵塞问题。出现这些问题的原因也比较多,第一,就是施工中出现的问题,大多是施工单位没有选择合格的管材,为了一时经济利益以次充好,或者是在安装前没有进行漏水实验,也或是一些不合格的材料运用到工程中导致漏水现象的发生;比如说管道穿墙(楼板)设置套管的缺陷与不足较为普遍。有的虽然加了套管,穿越楼板与楼板面齐平或嵌入楼板有的穿越墙面,比饰面多出20-50mm,有的没有设套管或预埋套管偏位,于脆用水泥圈(楼面)塑料圈(墙面)护(粘)住,掩人耳目,有的套管比管道只大一个规格,有的大三至五个规格,套管与管道间隙有的用泡沫、油麻堵塞等等套管的设置应按(GB50242-2002)规范第规定.“安装在楼板内的套管,其顶部应高出装饰地面20mm,安装在卫生间及厨房内的套管,其顶部应高出装饰地面50mm,底部应与楼板底面相平,安装在墙壁内的套管其两端与饰面相平。穿过楼板的套管与管道之间缝隙应用阻燃密实材料和防水油膏填实。端面光滑。穿墙套管与管道之间缝隙宜用阻燃密实材料填实,且端面应光滑。管道的接口不得设在套管内”。第二,就是设计方面出现了问题,导致管道安装好以后容易堵塞;第三,就是住户使用时出现了问题。
3 建筑给排水施工的特点
管道安装具有的特点
在这几年里,给水管道的材料大多使用的是PP-R管和UPVC管。因为这两种管道具有轻便、耐高压、抗腐蚀、质量安全、使用卫生、通水阻力小、使用寿命较长的特性,所以安装中最明显的特点就是便于安装。对于PP-R管的安装来说,连接前要清除管道上附着的灰尘后,在按照严格的施工流程来进行安装,但是其中需要注意的是在在对管道进行热熔是一定不能旋转,以免加热过度,而且在管道连通后还要采取一定措施对其进行冷却。对于UPVC管的安装来说,安装时一定要使用排水胶粘结。在涂完胶以后还要注意的就是胶干时间,具体的时间应依据当地气候和温度的变化来进行调节,还要注意不能沾水。如果是在环境温差较大的地方安装,必须使用管道伸缩节。
给排水管道的试压
当所有管道安装完成之后,还要对所有部位进行全面的检测,主要包括检测已安装的管道和阀门等设备是否符合设计和技术要求规定,如果有问题应立即拆除予以更换或是维修。检测的具体方法是用临时的短管来替代安装的管道,把所有的开口处封闭,从管道最低处开始灌水,在最高处进行放气。如果出现异样,要及时停止检测,并立即排水。在试压完成后,还对所有管道要进行吹洗。
4 提高建筑的给排水施工技术的具体措施
随着建筑技术的发展,生产工艺的不断改进和提高,对给排水工程的设计、施工、维修和运行管理的要求也就越来越高。要想使管网达到优质、高效、低能耗运行的目的,除要有合理的设计方案外,给排水系统安装质量的优劣将会对日后的使用产生极大的影响。
管道施工的措施
对于管道的施工来说主要是注意加热时间、加热温度、接缝压力这三个方面的问题,施工中运用最多的是钢塑复合管,在对其施工中应采用螺纹连接的方法,插入管道的长度应严格按照标准旋转深度进行控制;在对管端和管螺纹进行加工后,还要进行密封处理,这时需要使用聚四氟乙烯生料带来进行缠绕螺纹;施工中需要选用厌氧密封胶密封过的管道接头,必须在养护24h之后再进行试压。施工中要用专门的施工机具,不能随便更该。
W型铸铁管的施工方法
有关W型铸铁管的具体施工措施,第一步就是下料,在切割管材时要选用专门的切割工具,主要是保证管口的平直。第二步是连接,进行连接时先要松开卡箍,再取出内衬中的橡胶圈,把箍套和橡胶圈放在入管口的一侧,使管口对齐后,随后把橡胶圈放在接口上,最后锁紧了箍套紧固了螺丝就算完成了管道连接。第三步低支架的设置,对于一般的管材安装来说,如果每隔3m设置一个支架其实是可以的,但是对于W型无承口机制排水铸铁管接口来说就不行了,因为其属于柔性接口,当支架放在管道中间时,理论上可以将管道保持平衡,可是在实际工作中,找到重心点是很难的,所以经常无法保证管道接口的平滑,如果采用每隔设置一个支架的方法来进行布置,这样就可以很好地解决管道外观和管道坡度的问题。
建筑给排水施工的监管
给排水管道的设计与施工是一项很复杂的措施,其中关于管道的铺设和管道的安装都容易出现问题,所以有关管道施工的监督也是一项非常重要的方面。因为管道施工工期较长设计建筑工程的的许多阶段,所以监管也可以分为多个阶段来进行。
首先,在工程施工前期阶段的监管,在施工前就应该仔细阅读施工图纸,充分了解设计者的设计意图和目的,这样才能保证施工过程中不偏离设计图纸的要求,也不能在施工中随意变更设计方案。
其次,是在基础主体结构施工阶段的监管,在基础主体施工中,要注意排水系统的排水管和给水管的引入管在穿越建筑物或地下构筑物外墙处时,是否按设计要求预留好了足够的孔洞以及设置好的套管。
再次,就是装修阶段的监管,在装修施工阶段主要是对给排水管道系统安装阶段,主要是注意装修工程不能破坏原有的管道路线的设置或是预留管道的破坏,必须在明确所有管道布置之后再结合装修方案进行施工。
5 结束语
随着我国建筑技术的不断发展,对给排水工程的设计、施工和运行管理等方面的要求也越来越高。优质的安装施工质量和科学的管理是保障管网系统高效安全运行的必要条件。为了满足给排水建筑施工技术要求,提高施工质量,需要施工人员不断学习,提高自身的技术素质,只有这样,才能保证安装工程的质量,立足于建筑安装工程的基本建设。
参考文献:
[1] 王胜飞;民用建筑给排水工程施工质量常见问题及预防措施[J].中小企业管理与科技(下旬刊),2010,(08).
[2] 金生;建筑工程给排水施工常见问题解决措施探讨[J].现代商贸工业,2011,(09).
[3] 刘康;建筑工程给排水施工常见问题及解决措施研究[J].科技致富向导,2011,(01).
[4] 何新辉,魏晓斌.高层建筑给排水设计分析研究[J].中国房地产业,2011,(04).
[5] 李霞,高层建筑给水排水工程课程教学实践与探讨[J].山西建筑,2011,(01).
一、工程概况及基本资料本设计为某小高层。该建筑共12层 ,层高 单元式住宅 每单元2户 整楼分3单元。 每户拥有洗涤盆一个,地漏子一个(厨房),洗脸盆一个, 淋浴器一个 ,洗衣机一台, 坐式大便器一个 ,地漏子2个 。 室外引入管 水压24M 排水室外标高 选出给水设备 。二、参考书目 1.《建筑给水排水设计规范》 GB50015-20032.《给排水设计手册(第十一册、第二册)》 中国建筑工业出版社3.《建筑给排水设计手册》 中国建筑工业出版社4.《高层建筑给排水工程》 化学工业出版社 李亚峰主编5.《给排水工程专业毕业设计指南》 化学工业出版社 李亚峰主编6.《高层建筑民用建筑设计防火规范(2001年版)》 GB50045-957.《给水排水制图标准》 GB/T50106-20018.《建筑给排水工程(第四版)》 中国建筑工业出版社 王增长主编11.《建筑给排水工程设计实例》 中国建筑工业出版社 建设部建筑设计院编著12.《给水排水设计手册第1册-常用资料》15.《建筑给水排水及采暖工程施工质量验收规范》GB50242-200216.《建筑排水硬聚氯乙烯管到设计规范》 (CJJ29-89)17.《全国民用建筑工程设计技术措施 给水排水》 (建设部工程质量安全监督与行业发展司,中国建筑标准设计研究所编 计划出版社)
MECHANICAL PRELIMINARY DESIGN REPORT STADIUM 1.给排水设计 饮用水和污水 Design Water and sewage water .设计基础 - 甲方提供的设计任务书和市政管网综合图 - 建筑专业提供的条件图 - 国家现行的设计规范及有关规定设计简章 .Design bases Design Brief and Municipal integrated network drawing offered by the client. Condition drawings from architectural discipline. Current national design codes and related stipulations 2. 给水系统 通过一根DN200的进水管将水引入.水表安装在进水管上,离红线1米处.供水管在红线内连成环路管网,并接到供应楼的消防水池和给排水水池.由环路管网向必需的室外消火栓和绿化带的喷淋器供水. 2. Water supply system For water supply of this project, DN200 water intake pipes are led in. Water meters are installed on the intake pipes m away from the red line. The water supply pipes are connected into loop networks in the red line and then led to the fire pool and sanitary water pool in the supply buildings respectively. Necessary number of outdoor hydrants and sprinklers for green area will be provided on the loop networks. 设计范围 包括红线内的饮用水,污水,雨水,建筑消防. Design scope Design scope of this project includes water, sewage water, rainwater, fire-protection in the building, and water and sewage water within the red line. 给排水水池与消防水池分开,容量为100m3 .体操馆供水管埋地敷设. Sanitary water pool is separated from fire water pool, volume of sanitary water pool is 100m3. Water supply pipes for the stadium will be laid in the earth. 3.用水量标准 - 体育馆: 15升/顾客·日 K= - 宾馆: 150升/人·日 K= - 餐厅: 50升/顾客·日 K= - 工作人员: 25升/人·日 K= - 地面冲洗用水: 3升/m2日 - 冷却塔补水量:按用水量的2%计 - 未预见水量: 按日用水量20%计 - 消防用水: 消火栓:室内40升/秒,室外30升/秒,火灾延续时间为3小时; 自动喷洒按22升/秒,火灾延续时间为1小时 卷帘水幕用水升/秒·米,火灾延续时间为3小时; Water consumption standard - Stadium: 15L/visitor·day K= - Hotel: 150L/visitor·day K= - Restaurant: 50L/customer·day K= - Staff 25L/person·day K= - Floor cleaning: 3L/m2·day Make-up water for cooling tower: 2% of the actual cold water consumption. Unforeseen water consumption: 20% of the daily water consumption. Water for fire protection Hydrant: 40L/s indoor, 30L/s outdoor, fire duration time is 3h; Sprinkler: 22L/s, fire duration time is 1h; Drencher for rolling shutter: ·m, fire duration time is 3h; 在适当的位置设置饮用水机,在主进口为残障人设置两个饮用水机.为此饮用水系统安装循环泵.机房 设在地下室的水除了机房.当饮用水机不被使用时,应排空,以免水质腐败. 在客房和餐厅内设置电热水器,同时亦为热水供应设置循环泵. 在更衣间旁设置电热水器,为淋浴和洗盥供应热水. 为楼板清洁安装一定数量的水龙头. Some suitable places are supplied with portable water drinking units, two drinking units for disable people are provided at main entrances, for this portable water system, circulating pumps are adopted, the equipment room is located in water treatment center in the basement. When there is no use, portable water will be drained completely to avoid deterioration. Electric water heaters are installed in guest rooms and restaurant, also hot water circulating pumps will be provided for supplying hot water. Electric water heaters are installed near the changing and clothing rooms for supplying hot water for shower and washing. Certain number of water taps are installed for floor-cleaning. 4.用水量 最大日用水量:日 最大时用水量:220m3/时 Water consumption demand Maximum daily water consumption: Maximum hourly water consumption: 220m3/hour 却循环系统 冷却水循环系统采用机械循环系统.总冷却水用量为460m3/h.在供应楼顶设置三台超低噪音冷却塔(230 m3/h, 2x 115 m3/h).进水温度37Co,出水温度32Co .补充水量 9,6 m3/h.补充水由市政供水网直接提供. Cooling water circulation system There are cooling water circulation system in this project, cooling water for the refrigerators adopts mechanical circulation system. Total water consumption of cooling towers is 460m3/h. On roof of the supply building there are 3 ultra-low noise cooling towers (230 m3/h, 2x 115 m3/h), inlet temperature of 37Co, outlet temperature of 32Co, with make-up water of 9,6 m3/h. Make-up water of the cooling towers will be supplied directly by the municipal network. 在消防泵房内有消火栓泵(一个运行,一个备用),喷淋泵(一个运行,一个备用),卷帘雨淋泵(一个运行,一个备用).用于地下车库的泡沫喷淋设备,如报警阀,泡沫压缩罐,化学药剂泵安装在消防设备中心. 消防水箱和消防稳压装置分别安装在车库的四面墙. In the fire water pump room, there are hydrant pumps (one operation, one standby), sprinkler pumps (one operation, one standby) and rolling shutter drencher pumps (one operation, one standby). Fire equipment, which are used for the foam sprinkler system in underground garage, such as fire alarm valves, foam concentrated tank and chemical dosing pump, etc. are provided in fire equipment centers. Four fire water tanks and fire protection stabilized pressure devices are respectively located at four sides next to the garages. 消防用水 消火栓:室内按40升/秒,室外按30升/秒,火灾延续时间按3个小时计 自动喷洒按22升/秒,火灾延续时间按1小时计 卷帘水幕用水量 升/秒·米,火灾延续时间按3个小时计 消火栓:室内,室外用水量皆为756m3; 自动喷洒用水量为 m3; 卷帘水幕用水量为 270m3; 一次火灾用水量为; Water for fire protection Water consumption standard for fire protection Hydrant: 40L/s indoor, 30L/s outdoor, fire duration is 3h Sprinkler: 22L/s, fire duration is 1h Drencher for rolling shutter: ·m, fire duration is 3h Water consumption for fire protection Hydrant: indoor and outdoor water consumptions are 756m3 respectively Sprinkler: m3 Drencher for rolling shutter: 270m3 Water consumption for one fire: m3 消火栓的布置 在整个建筑物内沿墙,沿柱,沿走廊,风塔上及楼梯附近设有必要数量的室内消火栓,消火栓间距小于30米.消火栓管网水平,竖向皆成环状布置,消火栓箱内配有DN65消火栓一支,25米衬胶水龙带一条,φ19毫米喷咀水枪一支,并配消防卷盘(DN25消火栓一支,30米胶管,φ9毫米喷咀水枪一支)且设有可直接启动消火栓泵的按钮;在室内消火栓箱下设有磷酸铵盐手提式灭火器箱.室内消火栓系统在室外设有三组水泵接合器. Hydrant arrangement Necessary number of hydrants are installed indoors along the wall, columns, corridors, and staircases, at intervals of less than 30m. Hydrant networks are connected as a loop both horizontally and vertically. Inside each hydrant box, a DN65 hydrant, a 25m long rubber lined hose, a water nozzle of φ19mm, hose reel (a DN25 hydrant, a 30m long rubber lined hose and a water nozzle ofφ9mm), and a direct starting button for the hydrant pump are provided. Under each indoor hydrant box, a portable ammonium phosphate powder extinguisher box is installed. There are three sets of pump adopters being installed outdoors for the indoor hydrant system. 消防系统 防水泵房及消防水池 供水管DN200在红线内连成环路管网,管网上安装 一定数量的消火栓.两根DN200供水管分别引入供应楼内两个消防泵房内的消防水池.消防水池总容量不应小于4000m3, 每个为. Fire protection system Water pump room and water pool for fire protection The lead-in pipes (DN200) are connected as a loop inside the red line, on the loop, certain number of hydrants are water supply pipes (DN200) are led into the fire water pools at each fire water pump room in supplybuilding. In consideration of the importance of the project, the volume of the fire water pools should be not less than 4000m3, each is . 自动喷淋系统 自动喷淋系统安装在全建筑范围,除了室外和高于10 米的房间.喷淋泵安装在地下的消防泵房内.报警阀设置在地下的消防泵房内和中间的消防设备中心内,水流显示器设在每个防火分区内. Sprinkler system Sprinkler systems will be provided inside the whole building except outside areas and roomshigher than 10m, with sprinkler pumps installed in the underground fire water pump rooms. Alarming valves installed in underground fire water pump rooms and four fire equipment centers in the middle, water flow indicators are installed by fire compartments. 除了安装一个封闭喷淋系统,将为地下车库设置一个泡沫喷淋系统.餐厅内安装93oC启动的自动喷淋头,但在其它房间,仅安装93oC启动的普通和快速反应自动喷淋头.三组泵接合器安装在室外. Besides an enclosed sprinkler system, a foam sprinkler system composed of a proportioning mixer and a foam concentrated tank is provided for the underground garage. Sprinkler actuated at 93oC are provided in the restaurants, but in other rooms, only ordinary sprinklers and fast response sprinklers actuated at 68oC are provided. Three sets of pump adaptors for this system will be installed outdoors. 排水系统 为排水系统设置污水主立管和特别垂直排气管.排气管与污水管在每层连接,污水排出体操馆.餐厅的污水首先在油脂分离池中处理,然后排入室外排水网.给排水污水将被在化粪池收集和处理,然后排入市政排水管网.化粪池在输送区旁.最大天排水量为870m3/天. 9. Drainage system Main vertical sewage pipes and special vertical vent pipes are provided for the drainage system. The vent pipes are connected with sewage pipe at each floor; sewage water is drained out of stadium. Sewage water in the restaurants and garage are treated in the grease and oil separation tank, and then discharged into the outdoor drainage networks. Sanitary sewage water is collected and treated in the septic tank, then drained into the municipal drainage. The septic tanks are located besides the deliverycircle. Maximum daily drainage amount is 870m3/day. 卷帘水幕系统 地下车库设置有卷帘水幕系统.水幕泵安装在消防水泵房内,采用开式雨淋头,电动或手动控制.十组泵接合器安装在室外 Drencher system for rolling shutters Rolling shutter protected by drenchers are provided for the underground garage, the drencher pumps are installed in the fire water pump rooms, open drencher heads are selected, and are controlled both by electrically and manually. Ten pump adapters will be installed outdoors for this system. 地下室内污水设有污水坑,废水设有废水坑,生活污水,废水经潜污泵提升排至室外排水管网,潜污泵的启停皆由磁性浮球控制器的控制. 地下汽车库废水设有废水坑,废水经潜污泵提升排至室外,经隔油池处理后排入室外雨水管网. There are cesspits for sewage water and wastewater pits for wastewater in the basement, the sewage and wastewater is sucked up and drained to the outdoor drainage networks by submerged sewage pumps. Operation of the pumps is controlled by the magnetic floating ball controllers. Wastewater pits are provided for the underground garage, wastewater is sucked up and drained to outdoor oil separation tank by submerged sewage pumps, after treated, wastewater is drained to the outdoors rainwater networks. 在柴油发电机房,变配电房和通讯设备机房设低压二氧化碳气体灭火系统. Low pressure CO2 extinguisher systems are provided in diesel generator rooms, transformer substations and telecommunication equipment rooms. 在本建筑内按"建筑灭火器配置设计规范"在每个消火栓箱下设手提式灭火器箱,箱内设有必要数量的磷酸铵盐手提式灭火器. According to the Code for Design of Extinguisher Disposition in Buildings, portable fire extinguisher box, in which there are necessary number of portable ammonium phosphate powder extinguishers, will be installed under every hydrant box. 在每个消防电梯井底旁设有消防排水坑,废水经潜污泵提升排至室外. Fire water drain pit is provided at side of bottom of each fire elevator well, waste water will be sucked up and drained out by the pumps. 雨水系统 雨水排水屋顶采用压力流排水. 雨水设计重现期按P=10年计算,降雨历时为5分钟,暴雨强度公式按Q=(1+)/(t+)计算. 沿柱在屋面设置雨水沟.雨水通过雨水沟收集,然后进入雨水头和下排管,然后到室外雨水观察井. 10. Rainwater system Pressurized drainage system is adopted for roof rainwater drainage system. Here, return period P=10 years, rainfall duration is 5 minutes, stormwater amount is calculated by the following formula: Q=(1+)/(t+) Rainwater gutters are provided on roof along columns, skylight. Rainwater is collected in the gutter, then to rainwater heads and downpipes, and to the outdoors rainwater inspection wells. 11.管材 - 生活给水管,冷却塔补水管采用铜管,氩弧焊接. - 直饮水管采用不锈管. - 消火栓管,冷却循环管,水幕管,水泵吸水管采用焊接钢管,焊接. - 自动喷洒水管,雨淋水管采用热镀锌钢管,丝扣连接或卡压连接. -二氧化碳管采用无缝钢管焊接. - 地下车库泡沫喷淋水管采用不锈钢管,卡压连接. Pipe material Copper pipes connected by argon arc welding are adopted for the sanitary water pipes, make-up water pipes for cooling towers. Stainless stell pipes are adopted for portable water pipes. Welded steel pipes connected by welding are selected for hydrant pipes, cooling circulating pipes, drencher pipes, pump suction pipes. Hot-galvanized steel pipes connected by threads or compression-seizing are selected for sprinkler and deluge sprinler pipes. Seamless steel pipes connected by welding are selected for CO2 pipes. Stainless steel pipes connected by pressed clamp is selected for the pipes of foam sprinklers in the underground garage. 当雨水两超出雨水沟设计量时,雨水可沿屋檐自由排放.雨水被收集,然后排入市政集水池. When the amount of rainwater is more than the design value of the gutters, water is discharged naturally along the eaves. Rainwater is collected, and then drained to the municipal catch basins. 围绕体育馆的循环池将用于喷洒运动场和作为室外绿化带的储水池. 此池将作为一个循环过滤设施,可容水约 m . 喷洒压力设备和其它必须的过滤设备安装在供应楼里. The circular senic pool surround stadium will be used for spraying sportsfield and as reservoir for outdoor greening. The pool will be used as a circular filtering facility and will be adopted with a water volume of about m . The spray water pressurizing equipment as well as further necessary filtering equipment will be adopted in the supply building. 制冷 Cooling 冷源: 空调冷负荷(估算): 本工程建筑面积共平方米,包括观众区,休息室,更衣室,小会议室,餐厅,办公室和其它附属房.空调设计日峰值冷负荷为,设计日总冷负荷为3 kW. Refrigerating source Cooling load of air conditioning system Total floor area for this building is 50,000sqm, which includes spectator areas, lounges, Clothing and changing rooms small meeting rooms, restaurant, office and other auxiliary rooms. Designed dayly peak cooling load is 2,4MW, designed total dayly cooling load is 3kW. 每台1200kW制冷机配一台 流量为206m3/h离心泵.各配一台备用泵 一次泵采用压差旁路控制. 通过埋地敷管,向游泳体操馆供应冷冻水. A centrifugal pump with a flow rate of 103m3/h is provided for each 1200kW chiller. One operation pump with a standby corresponds to one chiller. Pressure difference branch control is adopted for primary pump Via earth laid pipes from supply building to gymnasium chilled water supply will be deliverded. 冷源的选择: 根据建筑的实际情况,3台制冷机将安装在供应楼内的冷冻机房.设计容量为4800kW. 为了实现能量的效率化使用,设计方案为,1台制冷机的出力为总设计容量的50%.而另2 台.每台出力为总设计容量的25%. 冷冻水系统的主要设备包括3台电动制冷机,一级冷冻泵,二级冷冻泵,自动控制阀等等.冷冻水的供/回水温度为-7/ 12°C. Selection of refrigerating source According to the real condition of the building, 3 chillers are located in the refrigerating plant rooms in the supply building, designed capacity is 2400kW. For actuing in an energy efficient way one chiller about 50% of total capacity ( kW) and two chillers with 25% of total (600 kW each)capacity each are adopted. Main equipment of chilled water system includes 3 electrical chiller, primary cool water pump, secondary chilled water pump and automatic controlled valve, etc. supply/return temperature of the chiller is-7/ 12°C. 二次泵系统:根据使用功能,各制冷机房又分成不同的循环支路. 二次泵采用变频调速控制.根据负荷侧供回水管的压差,控制水泵的转速. 二次泵循环支路的管道采用异程式. Secondary pump system: Each refrigerating plant room is subdivided into different circulation branch loops according to use functions. Variable-frequency speed-regulating control is adopted for secondary pumps. The rotating speed of a water pump is controlled according to the pressure difference between water supply and return pipes. Direct return system is adopted for the pipes of circulating branch of secondary pumps 空调冷冻水系统 由于本工程占地面积大,功能复杂,有连续使用,也有间歇使用,为了达到运行灵活,节能的目的,空调冷冻水系统采用两管制二次泵系统. Chilled water system Due to the large occupied area of this project, the complicated functions and the combination of continuous utilization and intermittent utilization, in order to accomplish the purpose of flexible operation and energy saving, the chilled water system is of two-pipe secondary pump system. 管材: 水管采用焊接钢管及无缝钢管. 本工程的风管除土建风道外,均采用镀锌铁皮咬口制作.每节风管之间用法兰连接. Pipe and duct materials The water pipes adopt welded steel pipes and seamless steel pipes. Air ducts for this project are made of galvanized sheet steel by seaming except ducts by civil construction. Air ducts are connected together by flanges. 一次泵系统: 供应楼冷冻机房 2400kW制冷机配一台离心泵, 流量为412m3/h.配一台备用泵. Primary pump system: Chiller room supply building A centrifugal pump with a flow rate of 412m3/h is provided for 1200kW chiller. One operation pump with a standby corresponds to one chiller. 保温材料: 空调供,回水管,冷凝水管采用酚醛管壳保温. 空调送,回风管以及处理后的新风管采用外贴铝箔的离心玻璃棉板保温. - 管道穿防火墙的空隙处采用岩棉材料等非燃材料填充. Thermal materials phenolic pipes are adopted for thermal insulation of water supply and return pipes for air conditioning, as well as air-conditioning condensate pipes. Aluminum foil faced glass fiber boards are adopted for thermal insulation of air-conditioning air supply and return ducts as well as fresh air ducts after chillers. Non-flammable material will be selected to fill the interspace in the fire protection wall where the ducts go through. 消声与隔振: 冷水机组,水泵等设备采用减振台座,弹簧减振器或橡胶减振垫减振降噪. 在空调机组,新风机组,通风机的进出口采用涂胶帆布软管连接. - 水泵进出水管上采用可曲挠橡胶接头,使设备振动与配管隔离. Noise reduction and vibration isolation Shock absorption bases, spring shock absorbers on rubber shock absorption pads are adopted for equipment, such as water chiller units, pumps, etc to reduce vibration and lower noise. Flexible rubber-coated canvas hoses are adopted far connections of inlets and outlets of air-conditioning units, fresh air handling units and ventilators. Flexible rubber couplings are adopted for the water intake and delivery pipes of the pumps to isolate equipment vibration from their pipes. 空调和通风系统 Air Conditioning and Ventilation Systems 方案设计范围 Scope of schematic design 空调设计 Air Conditioning Design 在体育馆内,一些区域设置空调系统.这些区域划分为: 西侧地下二层的贵宾休息室 东侧地下二层酒店门廊 地下一层的输送区,技术机房,运动员更衣间,医务服务,热身区,裁判区,健身中心,酒店大堂,会议室,厨房,特许区和贵宾大堂混合区. 首层的酒店大堂,酒店区,贵宾门廊,急救 In the stadium, in some ranges air conditioning systems are used. These ranges subdivide themselves as follows: VIP – Lobby in West of levelel -2 Hotel lobby in the east of level –2 Delivary Circle, technical Plantrooms, Changingrooms for the athletes, Medical Service and warm up area, Judges Area, Fitness Center, Hotel Lobby, Conferenz, Kitchen and Concession, Vip lobby- Mixed Zone in level -1 Hotel lobby, Hotel area, Vip lobby, Vip Area, First aid in 0
给排水工程对城市发展建设有着重要意义,因为给排水会影响到城市居民正常生活和社会稳定。下面是我为大家整理的给排水相关论文,供大家参考。
【摘要】看一个城市是否发达,不光要看GDP、高楼大厦,还要看人们看不到的地方,比如下水道等;看一个城市的规划是否合理,不仅要看楼间距、绿化程度,还要看人们需要的地方,比如给排水系统。给排水设计在城市规划中占有十分重要的地位,对满足城市居民的基本生活与工农业生产的供水、排水系统建设具有很重要的意义。
【关键词】城市规划,给水,排水
一、引言
城市给排水工程是对城市给水排水工程系统的统一安排,保证给水排水工程建设与城市发展相协调,促进城市的可持续发展。它是城市规划中的一项专业规划,也是城市整体开发建设的一个重要组成部分。它的综合作用是不能被代替的。城市水系统的规划与设计是否合理将直接影响和制约城市的发展。“城市水系统”主要包括水源系统、用水系统、给水系统、排水系统、回用系统和 雨水 系统。随着城市的发展,各个城市间的给排水工程不再是一个孤立的系统,水域把这些子系统连接为一个系统,原有的工程规划 方法 在一定程度上显示其局限性,这就要求我们在新的历史条件下做好城市市政给排水规划设计,认真思考与解决现存的问题,寻求城市水资源的合理利用,在经济和技术方面满足社会发展的要求,实现现代化城市的可持续发展。
二、城市给排水系统规划存在的问题
(1)市政给排水工程规划滞后。在市政道路排水工程设计过程中,给排水工种处于配合地位,影响了城市给排水规划科学化的发展。往往出现道路要求快速建设,造成了排水工程规划没有编制,一些排水工程往往不能与道路工程同期施工;有的虽然设计完成后,排水工程规划由于相关原因需要修改,许多工程项目未能按照规划进行建设,规划的指导意义也没有得到真正体现,造成了工程需要再次改造。
(2)规划的科学依据不足。城市水系统规划的基础性工作主要包括各类指标、标准、基础数据和分析工具,其中水量预测和水平衡分析是核心工作。目前,我国的水量预测工作主要是参照《城市给水工程规划规范》(GB50282-98)中有关规定,但我国不论在国家还是在区域层次上都缺乏对用水工艺、各种用水器具和用水行为的详实系统监测,缺乏对新型用水技术替代规律和扩散规律的基础研究,缺乏对多种用水信息的综合性和结构性分析。
(3)排水体制规划混乱、排水体制的不合理。目前绝大部分市区的排水设施分别由环保局、市政工程管理处、水利局等不同部门管理,由于各部门之间沟通不够,管理人员责任不清,加之相关法律法规不够健全,对排水设施存在的问题以及发生的新问题都不能及时解决。另外传统的防洪和排水设施设计中,强调采用分流制排水体制将雨水和污水尽快排出城市,但忽视了城市径流面源污染的控制和雨水资源的利用。随着流域整体水质的逐步改善,城市随机性暴雨径流和突发排放事件引起的对水体生态系统的冲击,已日益成为流域污染控制的主要内容。
(4)传统的给排水专业不能满足市场的需要。由于城市给排水规划设计技术参数多、不定因素多,且具有交叉学科的特点,这使城市给排水规划的难度大大增加,刚从传统的给排水专业 毕业 的学生,因受知识结构的限制,不能进行宏观的分析论证,不适应城市规划多学科、多层次的分析论证要求,远不能满足城市给排水规划设计的需要。
三、解决城市给排水系统规划问题的对策
(1)城市水系统规划要与城市规划的协调。城市水系统规划是对一定时期内城市的水源、供水、用水、排水、污水处理等子系统及其各项要素的综合布置。城市用水规划的总量平衡非常重要,必须优化组合各种可行的节水、水回用等方案。要做到这些,首先要了解城市水利用规划,加强城市总体规划中的水专项规划,按照水的可持续发展观念编制城市水利用规划,内容应包括:地面水、地下水、雨水和海水等水资源平衡;供水、排水和污水再生利用等总量平衡;供水节水规划和污水处理与再生利用规划;水的生态循环规划;各类水工程设施的规模和布局等。对当前我国的城市水系统建设中普遍出现的规划不协调、建设不配套、管理不统一等问题,规划中要特别注意管网配套和供水、排水及污水处理能力的协调增长,确定规划期内水系统及其网络设施建设的规模、详细布局和运行管理方案。
(2)加强水量规模预算。水量预测是给水规划的基础,水量规模预测是否符合发展趋势和实际需要,对水资源的工程总体布局、合理利用、实施步骤和工程费用产生重大影响。国家标准《城市给水工程规划规范》是测算城市总用水量规模的主要依据,具体包括:总体规划阶段给水水量预测;总体规划阶段污水水量预测;分区规划阶段及专业规划给水、污水量预测;详细规划阶段给水、污水量预测。改革开发以来,工业生产、城市建设、住宅建设、第三产业迅速发展,使供水量也不断增长。作为城市基础设施之一的供水量的增长规律也将与过去不同,水量预测就不能仅按历史的发展计算,还要根据具体的城市规划对不同类型用水量分别进行预测分析。
(3)城市给排水系统应当向可持续性方向发展。自然界的水是循环的,给水和排水是统一的,人类社会对水的使用应服从这一过程。在用水之后,必须对水进行再生处理,使水质达到自然界自净能力所能承受的程度,否则累积的大量污染物将超过水环境的容量,从而导致水资源危机和水污染现象,最后破坏水的良性循环,不利于城市的可持续发展。控制城市给排水系统向可持续性方向发展的途径有:①在城市水系统中增加节水子系统;②在城市水系统中增加治污子系统;③在城市水系统中增加再生水回用子系统。加强节水、治污和再生水回用力度,重视再生水、中水等非传统水资源利用,是促进城市给排水系统良性循环,实现城市水资源可持续发展的关键。
(4)完善各项法规。根据我国当今给排水体制规划混乱的现状,应通过行政立法,完善相关法规,建立明确的给排水工程建设及管理职责制度和相关体系,明确管理权限,形成规划、建设、维护、监督各部门明确的权利、职责和监管机制。
四、结束语。在现代城市整体规划中,给排水的设计是一项十分重要的工作内容。城市规划是为了对资源进行优化配置,给排水工程规划重点是对水资源进行优化配置和合理利用,以发挥最大的综合效益。城市给排水设计是否合理、完善,直接关系着城市的经济建设和人民的基本生活需求。因此,在规划与设计城市给排水规划时要善于发现问题,并妥善处理好城市发展中可能面临的水资源、水环境、水灾害问题。高质量地编制好城市给排水规划,不仅是排水工程规划与设计自身的需要,而且是城市面向未来,走上可持续发展之路的保障。
摘 要:市政给排水管道施工质量随时影响着城市居民的生活,为了保证市政排水施工的质量,做好给排水施工的安全 措施 与防范是我们的首要任务。市政排水工程一旦出现问题将会对市民产生很大影响,而且出现市政给排水工程的问题和解决问题都需要较长的时间。从技术方面分析市政给排水工程的控制质量,确保给排水系统功能的正常发挥,能够及时防范在施工过程中出现的一些障碍,保证施工的正常进行。
关键词:市政;给排水;施工质量
随着人民生活水平的不断提高与社会经济的不断发展,对市民用水的便捷性也提出了新的要求,因此市政给排水工程也成为市政建设不可忽视的一项工程。城市的建设发展离不开给排水管道工程建设,为保证城市稳步的发展,因此在市政工程施工过程中提高其施工技术和施工质量是关键一环。在其城市化水平的不断提高与发展的过程中,给排水工程对城市环保以及城市防洪排涝等都有直接的影响,因此对其施工技术要求也日益增加。给排水管道工程施工质量出现问题,可能会造成污水倒流,在雨季会由于排水不畅而在城市中形成内涝给人民的日常生活带来极大的不便,同时有损政府形象。加强市政工程给排水管道施工质量的监管与控制,对于城市水污染的治理以及水资源的节约利用具有重大的意义。
1 市政给排水施工
施工准备阶段。市政给排水工程项目是城市规划建设与发展的重要保障。作为城市建设的基础项目其质量的安全可靠关乎城市的形象,而且由于市区施工环境复杂,其地下结构也存在着许多地下管线。同时容易受到各种因素的干扰,给排水工程施工的难度大大增加。为了提高市政给排水管道系统的安全性和可靠性,不仅要对施工技术进行严格的要求,还要做好相应的准备工作,确保工程的施工质量。
(1)给排水管道工程施工前,应把各类进场技术人员、工种、材料和机具设备检查结果情况及现场施工条件等因素都要一一考虑进去。施工工艺、施工方案、组织措施以及准备工作关系到工程的顺利实施,做好准备工作是重中之重。工程施工前,工作人员要对设计的施工图纸等进行严格审核,应避免工程障碍对工程质量以及施工技术带来较大的影响。同时需要实地勘察现场的施工条件,根据事实设计图纸,尽量避免因设计与实际情况不符造成给后续施工加大工作量。施工人员要采用相关的技术手段对其可能存在的障碍进行全方位的调查与排除,避免施工中因地下出现各种管道与设计冲突而妨碍施工的现象。在专业图纸上,应明确施工要求,多方进行讨论与查漏补缺,纠正错误。
(2)管材质量是确保施工工程质量的基础,对各种管材之中容易出现的问题和缺陷进行严格控制,材料质量的优劣是影响其给排水功能正常有效发展的前提和关键。为有效防治和预防出现渗水和渗透问题应严格控制管材质量由专业的技术人员进行监管。施工过程中由于城市特有的特点交通繁忙设立必要的安全措施既是对工作人员的防护也是对市民出行安全的考虑。从可持续发展角度而言,在给排水工程中推广新型具有管道摩阻小、排水量大、重量轻、施工方便等特点塑料复合管材,符合国家以塑代钢政策。但限于国家的技术发展程度其使用材料也有可能对周围环境有一定的影响,因此我们除了积极克服技术问题,必要时还要和当地环境卫生部门进行相应的协商。
2 施工阶段
管槽开挖
在开挖之前,根据技术规范相关条款的规定做好原始地貌的中心线、高程、转角的原始记录。应该对地下既有管道,施工现场的电缆和其他构筑物存在的情况逐一查实探明,并标准它们的位置,为了保护其完好性以便于采取相应的保护措施。根据不同的土壤条件,开挖直槽、梯形沟槽、开挖混合管槽等不同的管槽,沟槽开挖宽度应根据开挖深度和管径大小确定。随着科学技术的不断提高,机械化施工技术水平有了很大的改善,机械施工取代了大量的人力劳动而成为工程施工的重要方法,人仍然是机械的操作者,应协调好人与机的关系,保质保量的完成施工。施工时应掌握天气变化, 防止沟槽内长期积水,形成浮管现象。考虑到基槽暴露时间过长会引起基槽变形的问题,要尽量缩短晾槽时间。在沟槽开挖将要结束时,应提前做好管道基础稳定准备,并对碎石形成的混凝土基础进行控制分析,及时处理施工过程中出现的各种质量隐患。严格按照标准铺设砂砾垫层并压实,在铺好的砂砾垫层上浇筑由设计人员按照工程实际情况和工程要求进行设计的具有一定刚度和稳定性性能的混凝土。因地面下的结构并非一成不变,防止机械化施工挖掘过量,一旦出现应及时进行回填和夯实,针对此出现的工作失误进行及时处理。
管道安装
管材进场后,由专门的技术人员检验合格后才能用于工程。为能够有效保证管路的密闭性需确保管材质量合格并确定密封胶圈完好现象。管道安装对接一般依靠管道顶部的外拉法和管道内部的内拉法,逐渐将两节管道对接在一起。为防止扰动基底管道相互碰撞需保证管节平稳的缓慢的下放,因此应有专人进行指挥铺管下管,管道放入后必须垫稳。具体方法可在 编织 袋内灌满砂石或黄砂,封口后压在已排设管道的顶部。进行管道铺设时确保管道表面无杂物,内部也干净。待管道铺设阶段完工后进行检测验收,检验结果合格后就可进行混凝土管座及接口施工。当接口合拢时为保证已排设管道轴线位置的稳定,需采取稳管措施,防止轴线出现偏移。管道接口后,应复核管道的高程和轴线使其符合要求。安装时使内壁平齐,对口准确。焊缝表面光顺、饱满、均匀,错口误差小于 倍壁厚。其宽度、表面余高、咬边、错边等均符合设计规范要求。对管道焊接质量要进行油渗试验和 X 射线无损探伤检测仪进行检测,检测合格后管道安装才算合格。
闭水试验
当管道安装完毕后,确保管道沟槽内无积水、预留孔洞均封堵且不漏水,有工作技术人员检查管道及检查井外观质量是否合格。若经检验合格,在对管槽进行回填前,应对重力流、设计要求闭水的管道以及压力管道都必须做水压试验。在排水管路施工质量检测的多种方法中,闭水实验对其施工质量的检测属于最直观、最有效的方法。将排水管道从上游向下游分段依次试验。试验满水浸泡一天之后,按照实验要求的试验水头达到规定水头,对管道不断渗水量观测持续半小时以上,实测渗水量是否满足排水管道闭水试验施工要求规范规定的允许渗水量。检查每一处管路的防漏性,是否存在渗水部位、漏点、裂缝等。闭水实验同时也可测定各管连接接口的密闭性,如发现有渗漏,应及时采取修补措施,可调制水泥浆对漏点处进行修补和填实。
3 市政给排水施工质量控制要点
在城市的市政给排水工程中,整个市政给排水工程质量控制的最重要环节是施工阶段。做好市政给排水工程施工质量的控制是对整个工程的安全措施的保障。为满足管道安装的所需条件,结合管道的设计要求及纵向位置适当调整该处的道路基础。给排水管道穿越软弱土地区时,压力管道一般采用柔性连接管道接口,以增强其变形能力, 同时进行适当的地基处理和防腐措施。对管道进行严格的防腐处理,应选用防腐性能好的管材产品。管槽开挖时要采取适当的技术措施,保护好地基处理成果不被破坏,并对回填土进行严格控制。
4 结语
为保证市政给排水施工质量,需要工程的负责人针对每个工程的施工环节都做到认真仔细严格把关。针对市政给排水工程在建设施工中的施工的技术和质量都要进行反复的检查,这关系到整个给排水工程的质量。采用科学先进的施工技术,这样才能够使给排水工程的施工质量得到有效地控制,才能够使市政排水系统在施工完成后能够正常有效地发挥其功能。同时借鉴国外的大城市给排水系统设计完善我国面临的难题,提高市政工程质量。
参考文献:
[1]张胜霜.浅析市政给排水施工质量控制技术[J].科技创新与应用,2014(08).
[2]潘政委.市政给排水管道工程施工优化探讨[J].中国新技术新产品,2011(22)
【摘 要】给排水工程施工管理主要以建设、施工项目作为管理对象,不断进行全面系统管理和优化的管理与控制活动,即是从施工项目开始到项目竣工完成过程中,通过一系列的项目控制与管理措施,以确保质量管理目标、成本管理目标以及安全管理目标的顺利实现。为全面保证施工质量,以下就给排水工程中的施工前、施工中以及施工后三个阶段分别进行了阐述。
【关键词】给排水工程;施工;管理
1.施工准备阶段
做好图纸会审工作
图纸会审是施工准备阶段的一项重要组成部分,做好图纸会审能有效促进给排水施工的正常进行。依据给排水工程的基本特点,应抓好以下几方面工作:设计图纸是否符合国家技术规范标准、当地相关政策的具体规定以及是否满足建设单位的基本要求;设计是否具备进行施工的技术条件,采取先进的技术措施和施工工艺时,是否能保证技术上的施工安全;设计图纸上坐标、标高和尺寸等是否符合实际建筑构件的要求,洁具设备的安装位置是否恰当,以及材料的规格、尺寸等是否合乎规定的基本要求;消防设备以及基础设施的具体位置应提前上报当地主管部门得到审查认可,并确定具体的施工要求;加强各专业之间的协调工作,做好土建预留、预埋孔洞和设备安装位置的技术交底工作。
加强施工组织设计
承包商应加强施工组织设计工作,并将具体施工方案提交给监理和业主进行审核。施工组织方案应突出体现设计图纸的可行性、合理性和安全性的基本原则,重点关注组织方案的技术和质量措施,是否完全符合 承包合同 规定的基本条件和具体要求,确保安全和文明施工并确保切实符合相关规范的有关规定;工程专业技术人员应认真掌握设计图纸内容,相关验收规范等,通过对承包商提交的施工组织设计进行严格的审查,审查对象主要是专业工程部分和承包商分包工程部分,详尽了解施工企业的综合技术和管理水平,以便进行有重点的预控和管理力度。
严格材料、设备质量控制
给排水施工所需材料、设备,在施工前由施工单位填写《工程材料使用报审表》,为保证材料、设备的质量以及各种性能指标符合技术标准要求,应安排采购部门统一进行采购和管理。应依据排水设计施工图规定的规格、型号等以及施工要求进行采购,所选购材料、设备必须具备合格证、质保书以及相关检测 报告 等相关认证资料,特殊材料需经相关质检部门检验合格后方可使用,所有运至施工现场的材料和设备,均必须做好防雨、防潮等保管防护工作。
2.施工阶段的管理工作
做好组织、协调和管理工作
给排水工程在建筑整体工程中占有相对较小的比重,但其涉及面广,工序复杂,专业工种多,因而必须加强组织、协调和管理工作。应严格混凝土浇筑的审批程序,由专业工程师进行现场指导,做好土建和给排水安装作业的协调配合,重点强调预留、预埋孔洞的具体位置和实际尺寸,以避免后续施工由于土建预留预埋的失误而开凿墙板造成返工。施工单位应及时和设计单位进行沟通,以便及时攻克施工过程中的诸多技术和管理问题,应严格控制设计的变更,设计变更必须经过多方周密细致分析讨论后实施。另外,必须经过给排水专业工程师签名确认后,方可进行混凝土的浇筑。
做好土建施工的预留、预埋工作
为防止后续施工进行楼板开凿而严重破坏建筑物结构,在进行土建施工时应将管道穿越楼板位置预留适当的孔洞,同时在管道穿越地下室外墙的具体位置,也必须预埋合适的套管,以避免外墙产生渗漏现象。因此,一定要严格和土建施工的密切配合,并确保管道穿越位置预留、预埋孔洞、支架以及钢构件等完全符合设计要求。应确保预埋在管道穿越楼板处套管的顶部比装饰地面高出20mm的距离,预埋在厨房、卫生间内的套管的顶部应比装饰地面高出50mm的距离,同时应使套管底部保持和楼板底面齐平,预埋在穿越墙壁位置的套管,保持其两端和饰面齐平,禁止随意开凿孔洞。依据设计施工图纸的基本要求,认真掌握管道配件的尺寸大小,在进行混凝土浇注前应制出预留套管的样图,作为指导预埋预留孔洞施工的参考依据。
做好主体结构的装修施工
进行主体结构装修施工是给排水工程施工中的重要环节,管道穿越主体结构的伸缩缝、沉降缝等后浇带时必须安装补偿装置。安装立管之前,需要将该立管在各部位预留预埋孔洞打通,由上往下垂直吊线,并准确测出立管的垂直中心线作为安装立管的参照线。立管施工完毕后,应严格检查其是否合乎垂直度和墙之间的距离比例要求,是否合乎设计施工的具体要求,待确定一切达到标准后利用管卡将其固定,并按照设计施工规范要求将各位置孔洞修补平整。排水立管应依照设计规定,在其中心位置距地面大约为处设置检查口,同时应在排水立管底部按具体要求设置合适的支墩。套管和管道之间的缝隙采用阻燃细密材料进行填实至端面平滑为止,并确保管道接口不要设置在套管内。吊顶内以及墙体内的排水管在施工完毕后,均应通过严格的闭水试验进行检测;排水立管、干管等必须做严格的通球试验,确保符合要求时及时进行隐蔽工程手续验收工作。
加强隐蔽工程的质量控制
给排水系统的管材、管件以及设备的质量必须符合设计施工规定的要求,应认真检查管道是否畅通后,再确定进行施工,施工完毕后再复检管道是否畅通;隐蔽工程的给水管道必须严格通水检测,安装完毕后的给水管道依据相关规定标准要求采取加压试验进行检测。隐蔽之前依照图纸要求检查各方面是否遗漏,安装位置、操作方法等方面是否满足设计的规范要求,经过水压、闭水和灌水试验,并通过验收合格方可进行工程的隐蔽工作。
3.施工后期的管理
严格施工后的质量把控验收工作,做好工程信息资料的收集整理工作,并依照专门的验收规范和标准进行工程的验收,尤其要加强隐蔽工程、被检验项目的质量验收工作,及时发现问题,找出原由并按合理的程序加以处理,亦或采取各种措施和方法进行调整和整改,将各种问题隐患消灭在萌芽状态,待各项整改措施验收合格后才能进入后续工序或分项施工。只有各项检测和验收符合规定的标准后,方可进行分部、分项工程的验收工作。在未进行工程竣工的验收移交前,要加强工程资料的收集和整理工作,以确保给排水工程的合理运行和管理。
4.结语
给排水工程必须严格依照国家技术标准的具体要求,确保完全符合相关的施工质量验收规范。为了满足于理想的施工管理水平,应严格组织设计施工管理,加强各工序和各环节的工序质量控制,重点突出施工管理中的难点进行改进和革新,并不断完善施工的质量管理措施,以确保给排水工程的整体施工质量。
【参考文献】
[1]熊湘捷.浅析给排水工程存在问题及控制措施[J].福建建材,2007,(06).
[2]刘洋,宋德全.浅谈建筑给排水施工中的安全和质量管理[J].中国新技术新产品,2009,(04).
[3]葛贤平.浅议建筑给排水施工质量的保证措施[J].中国新技术新产品,2009,(06).
1. 高层建筑给排水论文
2. 工程项目管理论文参考范文
3. 浅谈智能建筑相关论文
4. 浅谈工程项目管理论文
5. 浅析工程技术管理论文
6. 高层建筑施工管理论文
随着我国现代建筑技术的不断发展,人们对于建筑给排水工程方面也提出了越来越高的的要求。下文是我为大家整理的关于建筑给排水工程论文的范文,欢迎大家阅读参考!
浅谈高层建筑给排水工程设计
摘要:对高层建筑给水系统设计,排水系统设计、室内消防和热水系统设计进行了详细介绍,总结出目前高层建筑给排水存在的问题,并探讨了给排水节水措施,以确保水资源的合理利用。
关键词:建筑给排水;高层建筑;设计;节水措施
1、高层建筑给排水工程设计方法
高层建筑给水排水工程与一般多层建筑和低层建筑给水排水工程相比,基本的理论和计算方法是一致的,但因高层建筑层数多,高度大,结构复杂。近年来建筑给水工程设计方法得到改进。
例:给一个高层建筑为15层的楼房设计给排水:
住宅楼为框架结构,共15层,层高,室外给水管网位于建筑物的北侧,距离外墙为10m,接管点埋深,管径400mm,管材为球墨给水铸铁管,常年提供的水头;室内粪便污水需要经过化粪池处理方可排入市政管网,室外排水管网位于建筑物的南侧,埋深2m,管径600mm,管材为聚乙烯双壁波纹排水塑料管。
设计参数
生活用水定额:qd=150L/(人.d);最大小时生活用水量:Qh=;最高日用水量:Qd=;小时变化系数:kh=;每户人口:m=人;共90户;室内消防用水量:10L/s;消防水箱水量为火灾前10min的水量6m?;贮水池内的消防水量:按火灾延续2h的水量计;雨水重现期:2年。
设计内容
给水系统设计
管道采用钢塑复合管(内衬塑外镀锌)螺纹连接,进行干管安装、立管安装、支管安装,管道安装完毕需进行水压试验,压力设在,并对安装好的管道做好防腐和保温工作,冲洗管道对其进行管道通水试验。
根据《建筑给排水设计手册》上卫生器具的最大静水压力不得超过,因此高层建筑给水系统必须分区。设计任务书给定了市政给水管网提供常年的水压为。根据给水最小所需压力估算方法:第1层,第2层,2层以上增加1层,压力需增加。得的压力能直接供到第6层还多。所以1层~6层为一个区,上面7层~15层为一个区,总共就两个区。1层~6层用市政管网直接供水,其中底层和2层~6层单独设立管。
考虑到此设计对象是15层的高层建筑。市政管网提供的压力不能全部直接供水,所以必须对生活用水进行提升或加压。高层建筑设计一般都使用高位水箱供水,供水压力比较稳定,此设计也使用高位水箱;又因此设计面向高层民用住宅楼,通过查看平面图纸,根据建筑物的布置情况和楼层的承载力情况及水箱本身占用大量的建筑面积,即在楼层中间没有建筑面积可允许安置水箱,串联供水不可实现,因此高区的供水应在地面用泵抽升到高区水箱。
方案(一)与方案(二)相比管材使用量、工程投资相对较少,但它对减压阀的质量要求相对较高,一旦减压阀受损或使用性能降低,低区的静水压力会迅速增加,影响卫生器具的使用。方案(二)采用低区市政管网直接供水,消除了通过依赖减压阀降低静水压力来减少低区供水的现象。基于工程质量和供水水质及水压的可靠性,最终选择方案(二)
排水系统设计
室内排水系统为污水、废水合流系统,地上部分直接排出室外,地下部分分段设置集水坑把地下室污水、废水汇集于坑内,利用潜水泵由集水坑自动控制将其提升至室外。为了保护存水弯水封性能,保持排水系统内的空气压力与大气压取得平衡,使排水管内排水畅通,向排水管内通入新鲜的空气,保持管内的换气,防范因室外管道系统积聚起来的有害气体而伤害到养护人员、引发火灾和腐蚀管道等隐患,还应减少排水系统的噪声,在排水系统中设置通气管。
室内消防工程
室内消火栓给水系统有:分区、不分区两种方式。消火栓的静水压力超过时就需要分区供水,而本设计是15层的小高层,高度不超过50m,静水压力小于,可以不分区。同时本设计的建筑是15层小高层民用住宅楼,造成火灾的隐患少,人员疏散也快,扑救难度不大,高压消防给水无须设置常年的。设置专用的消防泵,从贮水池内抽取消防水,可用生活给水箱在火灾发生初期10min提前给水,并设置止回阀,既消除了消防水箱对楼层负荷,又可减少工程投资。此设计是15层小高层,层高,总楼高不超过45m,根据建筑给排水设计手册!规定消防栓的最大静水压力不超过,此设计无须分区消防供水,可利用消防泵直接供水满足条件。
室内热水工程
应根据建筑物的用途、热源的供给情况、热水用量和卫生器具的布置情况进行技术和经济比较来确定何种热水供应方式。热水供水方式有如下几类。按供应范围不同有:集中供热、局部供热、区域供热。
2、目前建筑给排水存在的问题
控制超压出流产生的水量浪费
生活给水系统按规定竖向分区后仍然存在着部分卫生器具配水点水压偏大的问题,而这是常常被忽视的。卫生器具的额定流量少于单位时间内的出水量,影响给水系统正常分配水的流量。如不采取减压节流措施,将造成水资源浪费、水压过高、漏水量增加等弊病,同时易产生水击、噪声和振动,致使管件损坏和破裂。这些水量的浪费不容忽视。
管道和阀门的损坏
我们可看到的路边给水管道在管子接缝处及法兰、阀门连接处向外冒水,而我们看不见的地下更不知有多少漏水处。管道受损及腐蚀,阀门不严等问题导致大量水流失。
热水系统浪费水量巨大
建筑热水供应已成为建筑给水的重要部分,由于设计不当,其浪费已非常严重,造成一定损失。所以给水系统供水应保证冷热水压力均衡,采用循环系统以确保每户开龙头就有热水,降低水量浪费。
3、我国建筑给排水节水措施
提高用水效率
1)严格执行生活用水量定额标准,饮用水、生活用水、景观用水、绿化用水按各个水质要求分别供给。
2)采用节水系统,如节水的卫生器具,利用限制卫生器具的流出水头、红外线感应龙头和便器等。
3)选择一个可再生能源,如风能、太阳能、水能、海洋能、地热能、生物能等非化石能源用于建筑的热水供应。对于不同的场合采用不同的热源形式。
雨水的利用
利用雨水收集系统再循环得到符合标准的水质进行绿化浇灌,处理后的雨水还可用于冲洗厕所,这不仅可减少用水量还可减轻污染。提高地基的保水能力,合理规划雨水流经途径,引入雨水沉淀池再利用。
污水排放和二次利用
建筑中水系统是典型的资源可持续利用装置,将建筑物产生的污水、废水加以收集并对其处理,在节省资源和保护环境的基础上对生活污水和废水的重复利用。
节水指标
节水指标有三类:
1)雨洪水利用率:常年降雨量除以使用或收集量;
2)水使用率:正常使用量除以使用量;
3)循环量:一次性用量乘以循环次数。
4、结语
在给排水设计时,我们应正确合理的选择系统和方案,以达到节水节能的目的,确保水资源的合理利用。
参考文献:
[1]孙志魁.我国绿色建筑给排水节能新技术的应用新探.中国新技术新产品,2012(1):45.
[2]杨天峰,张旺.低碳经济下建筑给排水的节能问题研究.科技创业月刊,2010,23(9):161-162.
[3]赵培林.浅议绿色建筑住宅的节水设计.机电产品开发与创新,2009,22(3):40-41.
[4]李倩.绿色建筑给排水设计的节水途径探析.企业导报,2012(1):273.
浅析建筑工程给排水施工技术
摘要:本文作者结合实际工作经验,对建筑工程的给排水施工技术进行了分析,提出了自己的见解。
关键词:建筑工程;给排水;施工技术
随着我国现代建筑技术的不断发展,人们对于建筑给排水工程方面也提出了越来越高的的要求。在设计和施工时要不断积累经验,深入分析各种常见问题,促进给排水施工技术的发展。
1 建筑给水方面的管道施工
给水管道材料的种类和选用
现在在新型建筑中用的较多的给水管材主要包括:聚丙烯类、聚乙烯类、聚丁烯类、工程塑料类,以及还有一些复合管类,例如:钢塑管、铝塑管、铜塑复合管等。虽然可供选择的材料有许多种,但在每一个具体施工工程中也必须根据实际情况进行选择。而且在管材的选用上还受到许多因素的影响,必须对国家政策、施工标准、地区特点、工程性质以及施工标准等因素进行综合考虑,选择最优管材。其中还要特别注意的是,管道的使用位置以及其使用方法是在管材选用时需要着重考虑的,还有就是管件与连接也是选取管材时容易忽视的一个关键的问题。
给水管道的施工
在对给水管做热熔连接时,必须要掌握好加热的时间和连接将要插入的深度。如果加热时间过长就使水管融化,如果加热时间过短也不能更好连接;如果插的过深,就会造成管道断面减少;如果插的过浅也会使降低接口处强度。所以,加热时的温度、加热时间和接缝压力是影响热熔连接质量的三个关键因素。
2 建筑排水管道常见问题的原因分析
排水管道方面经常出现的问题是漏水、堵塞问题。出现这些问题的原因也比较多,第一,就是施工中出现的问题,大多是施工单位没有选择合格的管材,为了一时经济利益以次充好,或者是在安装前没有进行漏水实验,也或是一些不合格的材料运用到工程中导致漏水现象的发生;比如说管道穿墙(楼板)设置套管的缺陷与不足较为普遍。有的虽然加了套管,穿越楼板与楼板面齐平或嵌入楼板有的穿越墙面,比饰面多出20-50mm,有的没有设套管或预埋套管偏位,于脆用水泥圈(楼面)塑料圈(墙面)护(粘)住,掩人耳目,有的套管比管道只大一个规格,有的大三至五个规格,套管与管道间隙有的用泡沫、油麻堵塞等等套管的设置应按(GB50242-2002)规范第规定.“安装在楼板内的套管,其顶部应高出装饰地面20mm,安装在卫生间及厨房内的套管,其顶部应高出装饰地面50mm,底部应与楼板底面相平,安装在墙壁内的套管其两端与饰面相平。穿过楼板的套管与管道之间缝隙应用阻燃密实材料和防水油膏填实。端面光滑。穿墙套管与管道之间缝隙宜用阻燃密实材料填实,且端面应光滑。管道的接口不得设在套管内”。第二,就是设计方面出现了问题,导致管道安装好以后容易堵塞;第三,就是住户使用时出现了问题。
3 建筑给排水施工的特点
管道安装具有的特点
在这几年里,给水管道的材料大多使用的是PP-R管和UPVC管。因为这两种管道具有轻便、耐高压、抗腐蚀、质量安全、使用卫生、通水阻力小、使用寿命较长的特性,所以安装中最明显的特点就是便于安装。对于PP-R管的安装来说,连接前要清除管道上附着的灰尘后,在按照严格的施工流程来进行安装,但是其中需要注意的是在在对管道进行热熔是一定不能旋转,以免加热过度,而且在管道连通后还要采取一定措施对其进行冷却。对于UPVC管的安装来说,安装时一定要使用排水胶粘结。在涂完胶以后还要注意的就是胶干时间,具体的时间应依据当地气候和温度的变化来进行调节,还要注意不能沾水。如果是在环境温差较大的地方安装,必须使用管道伸缩节。
给排水管道的试压
当所有管道安装完成之后,还要对所有部位进行全面的检测,主要包括检测已安装的管道和阀门等设备是否符合设计和技术要求规定,如果有问题应立即拆除予以更换或是维修。检测的具体方法是用临时的短管来替代安装的管道,把所有的开口处封闭,从管道最低处开始灌水,在最高处进行放气。如果出现异样,要及时停止检测,并立即排水。在试压完成后,还对所有管道要进行吹洗。
4 提高建筑的给排水施工技术的具体措施
随着建筑技术的发展,生产工艺的不断改进和提高,对给排水工程的设计、施工、维修和运行管理的要求也就越来越高。要想使管网达到优质、高效、低能耗运行的目的,除要有合理的设计方案外,给排水系统安装质量的优劣将会对日后的使用产生极大的影响。
管道施工的措施
对于管道的施工来说主要是注意加热时间、加热温度、接缝压力这三个方面的问题,施工中运用最多的是钢塑复合管,在对其施工中应采用螺纹连接的方法,插入管道的长度应严格按照标准旋转深度进行控制;在对管端和管螺纹进行加工后,还要进行密封处理,这时需要使用聚四氟乙烯生料带来进行缠绕螺纹;施工中需要选用厌氧密封胶密封过的管道接头,必须在养护24h之后再进行试压。施工中要用专门的施工机具,不能随便更该。
W型铸铁管的施工方法
有关W型铸铁管的具体施工措施,第一步就是下料,在切割管材时要选用专门的切割工具,主要是保证管口的平直。第二步是连接,进行连接时先要松开卡箍,再取出内衬中的橡胶圈,把箍套和橡胶圈放在入管口的一侧,使管口对齐后,随后把橡胶圈放在接口上,最后锁紧了箍套紧固了螺丝就算完成了管道连接。第三步低支架的设置,对于一般的管材安装来说,如果每隔3m设置一个支架其实是可以的,但是对于W型无承口机制排水铸铁管接口来说就不行了,因为其属于柔性接口,当支架放在管道中间时,理论上可以将管道保持平衡,可是在实际工作中,找到重心点是很难的,所以经常无法保证管道接口的平滑,如果采用每隔设置一个支架的方法来进行布置,这样就可以很好地解决管道外观和管道坡度的问题。
建筑给排水施工的监管
给排水管道的设计与施工是一项很复杂的措施,其中关于管道的铺设和管道的安装都容易出现问题,所以有关管道施工的监督也是一项非常重要的方面。因为管道施工工期较长设计建筑工程的的许多阶段,所以监管也可以分为多个阶段来进行。
首先,在工程施工前期阶段的监管,在施工前就应该仔细阅读施工图纸,充分了解设计者的设计意图和目的,这样才能保证施工过程中不偏离设计图纸的要求,也不能在施工中随意变更设计方案。
其次,是在基础主体结构施工阶段的监管,在基础主体施工中,要注意排水系统的排水管和给水管的引入管在穿越建筑物或地下构筑物外墙处时,是否按设计要求预留好了足够的孔洞以及设置好的套管。
再次,就是装修阶段的监管,在装修施工阶段主要是对给排水管道系统安装阶段,主要是注意装修工程不能破坏原有的管道路线的设置或是预留管道的破坏,必须在明确所有管道布置之后再结合装修方案进行施工。
5 结束语
随着我国建筑技术的不断发展,对给排水工程的设计、施工和运行管理等方面的要求也越来越高。优质的安装施工质量和科学的管理是保障管网系统高效安全运行的必要条件。为了满足给排水建筑施工技术要求,提高施工质量,需要施工人员不断学习,提高自身的技术素质,只有这样,才能保证安装工程的质量,立足于建筑安装工程的基本建设。
参考文献:
[1] 王胜飞;民用建筑给排水工程施工质量常见问题及预防措施[J].中小企业管理与科技(下旬刊),2010,(08).
[2] 金生;建筑工程给排水施工常见问题解决措施探讨[J].现代商贸工业,2011,(09).
[3] 刘康;建筑工程给排水施工常见问题及解决措施研究[J].科技致富向导,2011,(01).
[4] 何新辉,魏晓斌.高层建筑给排水设计分析研究[J].中国房地产业,2011,(04).
[5] 李霞,高层建筑给水排水工程课程教学实践与探讨[J].山西建筑,2011,(01).
MECHANICAL PRELIMINARY DESIGN REPORT STADIUM 1.给排水设计 饮用水和污水 Design Water and sewage water .设计基础 - 甲方提供的设计任务书和市政管网综合图 - 建筑专业提供的条件图 - 国家现行的设计规范及有关规定设计简章 .Design bases Design Brief and Municipal integrated network drawing offered by the client. Condition drawings from architectural discipline. Current national design codes and related stipulations 2. 给水系统 通过一根DN200的进水管将水引入.水表安装在进水管上,离红线1米处.供水管在红线内连成环路管网,并接到供应楼的消防水池和给排水水池.由环路管网向必需的室外消火栓和绿化带的喷淋器供水. 2. Water supply system For water supply of this project, DN200 water intake pipes are led in. Water meters are installed on the intake pipes m away from the red line. The water supply pipes are connected into loop networks in the red line and then led to the fire pool and sanitary water pool in the supply buildings respectively. Necessary number of outdoor hydrants and sprinklers for green area will be provided on the loop networks. 设计范围 包括红线内的饮用水,污水,雨水,建筑消防. Design scope Design scope of this project includes water, sewage water, rainwater, fire-protection in the building, and water and sewage water within the red line. 给排水水池与消防水池分开,容量为100m3 .体操馆供水管埋地敷设. Sanitary water pool is separated from fire water pool, volume of sanitary water pool is 100m3. Water supply pipes for the stadium will be laid in the earth. 3.用水量标准 - 体育馆: 15升/顾客·日 K= - 宾馆: 150升/人·日 K= - 餐厅: 50升/顾客·日 K= - 工作人员: 25升/人·日 K= - 地面冲洗用水: 3升/m2日 - 冷却塔补水量:按用水量的2%计 - 未预见水量: 按日用水量20%计 - 消防用水: 消火栓:室内40升/秒,室外30升/秒,火灾延续时间为3小时; 自动喷洒按22升/秒,火灾延续时间为1小时 卷帘水幕用水升/秒·米,火灾延续时间为3小时; Water consumption standard - Stadium: 15L/visitor·day K= - Hotel: 150L/visitor·day K= - Restaurant: 50L/customer·day K= - Staff 25L/person·day K= - Floor cleaning: 3L/m2·day Make-up water for cooling tower: 2% of the actual cold water consumption. Unforeseen water consumption: 20% of the daily water consumption. Water for fire protection Hydrant: 40L/s indoor, 30L/s outdoor, fire duration time is 3h; Sprinkler: 22L/s, fire duration time is 1h; Drencher for rolling shutter: ·m, fire duration time is 3h; 在适当的位置设置饮用水机,在主进口为残障人设置两个饮用水机.为此饮用水系统安装循环泵.机房 设在地下室的水除了机房.当饮用水机不被使用时,应排空,以免水质腐败. 在客房和餐厅内设置电热水器,同时亦为热水供应设置循环泵. 在更衣间旁设置电热水器,为淋浴和洗盥供应热水. 为楼板清洁安装一定数量的水龙头. Some suitable places are supplied with portable water drinking units, two drinking units for disable people are provided at main entrances, for this portable water system, circulating pumps are adopted, the equipment room is located in water treatment center in the basement. When there is no use, portable water will be drained completely to avoid deterioration. Electric water heaters are installed in guest rooms and restaurant, also hot water circulating pumps will be provided for supplying hot water. Electric water heaters are installed near the changing and clothing rooms for supplying hot water for shower and washing. Certain number of water taps are installed for floor-cleaning. 4.用水量 最大日用水量:日 最大时用水量:220m3/时 Water consumption demand Maximum daily water consumption: Maximum hourly water consumption: 220m3/hour 却循环系统 冷却水循环系统采用机械循环系统.总冷却水用量为460m3/h.在供应楼顶设置三台超低噪音冷却塔(230 m3/h, 2x 115 m3/h).进水温度37Co,出水温度32Co .补充水量 9,6 m3/h.补充水由市政供水网直接提供. Cooling water circulation system There are cooling water circulation system in this project, cooling water for the refrigerators adopts mechanical circulation system. Total water consumption of cooling towers is 460m3/h. On roof of the supply building there are 3 ultra-low noise cooling towers (230 m3/h, 2x 115 m3/h), inlet temperature of 37Co, outlet temperature of 32Co, with make-up water of 9,6 m3/h. Make-up water of the cooling towers will be supplied directly by the municipal network. 在消防泵房内有消火栓泵(一个运行,一个备用),喷淋泵(一个运行,一个备用),卷帘雨淋泵(一个运行,一个备用).用于地下车库的泡沫喷淋设备,如报警阀,泡沫压缩罐,化学药剂泵安装在消防设备中心. 消防水箱和消防稳压装置分别安装在车库的四面墙. In the fire water pump room, there are hydrant pumps (one operation, one standby), sprinkler pumps (one operation, one standby) and rolling shutter drencher pumps (one operation, one standby). Fire equipment, which are used for the foam sprinkler system in underground garage, such as fire alarm valves, foam concentrated tank and chemical dosing pump, etc. are provided in fire equipment centers. Four fire water tanks and fire protection stabilized pressure devices are respectively located at four sides next to the garages. 消防用水 消火栓:室内按40升/秒,室外按30升/秒,火灾延续时间按3个小时计 自动喷洒按22升/秒,火灾延续时间按1小时计 卷帘水幕用水量 升/秒·米,火灾延续时间按3个小时计 消火栓:室内,室外用水量皆为756m3; 自动喷洒用水量为 m3; 卷帘水幕用水量为 270m3; 一次火灾用水量为; Water for fire protection Water consumption standard for fire protection Hydrant: 40L/s indoor, 30L/s outdoor, fire duration is 3h Sprinkler: 22L/s, fire duration is 1h Drencher for rolling shutter: ·m, fire duration is 3h Water consumption for fire protection Hydrant: indoor and outdoor water consumptions are 756m3 respectively Sprinkler: m3 Drencher for rolling shutter: 270m3 Water consumption for one fire: m3 消火栓的布置 在整个建筑物内沿墙,沿柱,沿走廊,风塔上及楼梯附近设有必要数量的室内消火栓,消火栓间距小于30米.消火栓管网水平,竖向皆成环状布置,消火栓箱内配有DN65消火栓一支,25米衬胶水龙带一条,φ19毫米喷咀水枪一支,并配消防卷盘(DN25消火栓一支,30米胶管,φ9毫米喷咀水枪一支)且设有可直接启动消火栓泵的按钮;在室内消火栓箱下设有磷酸铵盐手提式灭火器箱.室内消火栓系统在室外设有三组水泵接合器. Hydrant arrangement Necessary number of hydrants are installed indoors along the wall, columns, corridors, and staircases, at intervals of less than 30m. Hydrant networks are connected as a loop both horizontally and vertically. Inside each hydrant box, a DN65 hydrant, a 25m long rubber lined hose, a water nozzle of φ19mm, hose reel (a DN25 hydrant, a 30m long rubber lined hose and a water nozzle ofφ9mm), and a direct starting button for the hydrant pump are provided. Under each indoor hydrant box, a portable ammonium phosphate powder extinguisher box is installed. There are three sets of pump adopters being installed outdoors for the indoor hydrant system. 消防系统 防水泵房及消防水池 供水管DN200在红线内连成环路管网,管网上安装 一定数量的消火栓.两根DN200供水管分别引入供应楼内两个消防泵房内的消防水池.消防水池总容量不应小于4000m3, 每个为. Fire protection system Water pump room and water pool for fire protection The lead-in pipes (DN200) are connected as a loop inside the red line, on the loop, certain number of hydrants are water supply pipes (DN200) are led into the fire water pools at each fire water pump room in supplybuilding. In consideration of the importance of the project, the volume of the fire water pools should be not less than 4000m3, each is . 自动喷淋系统 自动喷淋系统安装在全建筑范围,除了室外和高于10 米的房间.喷淋泵安装在地下的消防泵房内.报警阀设置在地下的消防泵房内和中间的消防设备中心内,水流显示器设在每个防火分区内. Sprinkler system Sprinkler systems will be provided inside the whole building except outside areas and roomshigher than 10m, with sprinkler pumps installed in the underground fire water pump rooms. Alarming valves installed in underground fire water pump rooms and four fire equipment centers in the middle, water flow indicators are installed by fire compartments. 除了安装一个封闭喷淋系统,将为地下车库设置一个泡沫喷淋系统.餐厅内安装93oC启动的自动喷淋头,但在其它房间,仅安装93oC启动的普通和快速反应自动喷淋头.三组泵接合器安装在室外. Besides an enclosed sprinkler system, a foam sprinkler system composed of a proportioning mixer and a foam concentrated tank is provided for the underground garage. Sprinkler actuated at 93oC are provided in the restaurants, but in other rooms, only ordinary sprinklers and fast response sprinklers actuated at 68oC are provided. Three sets of pump adaptors for this system will be installed outdoors. 排水系统 为排水系统设置污水主立管和特别垂直排气管.排气管与污水管在每层连接,污水排出体操馆.餐厅的污水首先在油脂分离池中处理,然后排入室外排水网.给排水污水将被在化粪池收集和处理,然后排入市政排水管网.化粪池在输送区旁.最大天排水量为870m3/天. 9. Drainage system Main vertical sewage pipes and special vertical vent pipes are provided for the drainage system. The vent pipes are connected with sewage pipe at each floor; sewage water is drained out of stadium. Sewage water in the restaurants and garage are treated in the grease and oil separation tank, and then discharged into the outdoor drainage networks. Sanitary sewage water is collected and treated in the septic tank, then drained into the municipal drainage. The septic tanks are located besides the deliverycircle. Maximum daily drainage amount is 870m3/day. 卷帘水幕系统 地下车库设置有卷帘水幕系统.水幕泵安装在消防水泵房内,采用开式雨淋头,电动或手动控制.十组泵接合器安装在室外 Drencher system for rolling shutters Rolling shutter protected by drenchers are provided for the underground garage, the drencher pumps are installed in the fire water pump rooms, open drencher heads are selected, and are controlled both by electrically and manually. Ten pump adapters will be installed outdoors for this system. 地下室内污水设有污水坑,废水设有废水坑,生活污水,废水经潜污泵提升排至室外排水管网,潜污泵的启停皆由磁性浮球控制器的控制. 地下汽车库废水设有废水坑,废水经潜污泵提升排至室外,经隔油池处理后排入室外雨水管网. There are cesspits for sewage water and wastewater pits for wastewater in the basement, the sewage and wastewater is sucked up and drained to the outdoor drainage networks by submerged sewage pumps. Operation of the pumps is controlled by the magnetic floating ball controllers. Wastewater pits are provided for the underground garage, wastewater is sucked up and drained to outdoor oil separation tank by submerged sewage pumps, after treated, wastewater is drained to the outdoors rainwater networks. 在柴油发电机房,变配电房和通讯设备机房设低压二氧化碳气体灭火系统. Low pressure CO2 extinguisher systems are provided in diesel generator rooms, transformer substations and telecommunication equipment rooms. 在本建筑内按"建筑灭火器配置设计规范"在每个消火栓箱下设手提式灭火器箱,箱内设有必要数量的磷酸铵盐手提式灭火器. According to the Code for Design of Extinguisher Disposition in Buildings, portable fire extinguisher box, in which there are necessary number of portable ammonium phosphate powder extinguishers, will be installed under every hydrant box. 在每个消防电梯井底旁设有消防排水坑,废水经潜污泵提升排至室外. Fire water drain pit is provided at side of bottom of each fire elevator well, waste water will be sucked up and drained out by the pumps. 雨水系统 雨水排水屋顶采用压力流排水. 雨水设计重现期按P=10年计算,降雨历时为5分钟,暴雨强度公式按Q=(1+)/(t+)计算. 沿柱在屋面设置雨水沟.雨水通过雨水沟收集,然后进入雨水头和下排管,然后到室外雨水观察井. 10. Rainwater system Pressurized drainage system is adopted for roof rainwater drainage system. Here, return period P=10 years, rainfall duration is 5 minutes, stormwater amount is calculated by the following formula: Q=(1+)/(t+) Rainwater gutters are provided on roof along columns, skylight. Rainwater is collected in the gutter, then to rainwater heads and downpipes, and to the outdoors rainwater inspection wells. 11.管材 - 生活给水管,冷却塔补水管采用铜管,氩弧焊接. - 直饮水管采用不锈管. - 消火栓管,冷却循环管,水幕管,水泵吸水管采用焊接钢管,焊接. - 自动喷洒水管,雨淋水管采用热镀锌钢管,丝扣连接或卡压连接. -二氧化碳管采用无缝钢管焊接. - 地下车库泡沫喷淋水管采用不锈钢管,卡压连接. Pipe material Copper pipes connected by argon arc welding are adopted for the sanitary water pipes, make-up water pipes for cooling towers. Stainless stell pipes are adopted for portable water pipes. Welded steel pipes connected by welding are selected for hydrant pipes, cooling circulating pipes, drencher pipes, pump suction pipes. Hot-galvanized steel pipes connected by threads or compression-seizing are selected for sprinkler and deluge sprinler pipes. Seamless steel pipes connected by welding are selected for CO2 pipes. Stainless steel pipes connected by pressed clamp is selected for the pipes of foam sprinklers in the underground garage. 当雨水两超出雨水沟设计量时,雨水可沿屋檐自由排放.雨水被收集,然后排入市政集水池. When the amount of rainwater is more than the design value of the gutters, water is discharged naturally along the eaves. Rainwater is collected, and then drained to the municipal catch basins. 围绕体育馆的循环池将用于喷洒运动场和作为室外绿化带的储水池. 此池将作为一个循环过滤设施,可容水约 m . 喷洒压力设备和其它必须的过滤设备安装在供应楼里. The circular senic pool surround stadium will be used for spraying sportsfield and as reservoir for outdoor greening. The pool will be used as a circular filtering facility and will be adopted with a water volume of about m . The spray water pressurizing equipment as well as further necessary filtering equipment will be adopted in the supply building. 制冷 Cooling 冷源: 空调冷负荷(估算): 本工程建筑面积共平方米,包括观众区,休息室,更衣室,小会议室,餐厅,办公室和其它附属房.空调设计日峰值冷负荷为,设计日总冷负荷为3 kW. Refrigerating source Cooling load of air conditioning system Total floor area for this building is 50,000sqm, which includes spectator areas, lounges, Clothing and changing rooms small meeting rooms, restaurant, office and other auxiliary rooms. Designed dayly peak cooling load is 2,4MW, designed total dayly cooling load is 3kW. 每台1200kW制冷机配一台 流量为206m3/h离心泵.各配一台备用泵 一次泵采用压差旁路控制. 通过埋地敷管,向游泳体操馆供应冷冻水. A centrifugal pump with a flow rate of 103m3/h is provided for each 1200kW chiller. One operation pump with a standby corresponds to one chiller. Pressure difference branch control is adopted for primary pump Via earth laid pipes from supply building to gymnasium chilled water supply will be deliverded. 冷源的选择: 根据建筑的实际情况,3台制冷机将安装在供应楼内的冷冻机房.设计容量为4800kW. 为了实现能量的效率化使用,设计方案为,1台制冷机的出力为总设计容量的50%.而另2 台.每台出力为总设计容量的25%. 冷冻水系统的主要设备包括3台电动制冷机,一级冷冻泵,二级冷冻泵,自动控制阀等等.冷冻水的供/回水温度为-7/ 12°C. Selection of refrigerating source According to the real condition of the building, 3 chillers are located in the refrigerating plant rooms in the supply building, designed capacity is 2400kW. For actuing in an energy efficient way one chiller about 50% of total capacity ( kW) and two chillers with 25% of total (600 kW each)capacity each are adopted. Main equipment of chilled water system includes 3 electrical chiller, primary cool water pump, secondary chilled water pump and automatic controlled valve, etc. supply/return temperature of the chiller is-7/ 12°C. 二次泵系统:根据使用功能,各制冷机房又分成不同的循环支路. 二次泵采用变频调速控制.根据负荷侧供回水管的压差,控制水泵的转速. 二次泵循环支路的管道采用异程式. Secondary pump system: Each refrigerating plant room is subdivided into different circulation branch loops according to use functions. Variable-frequency speed-regulating control is adopted for secondary pumps. The rotating speed of a water pump is controlled according to the pressure difference between water supply and return pipes. Direct return system is adopted for the pipes of circulating branch of secondary pumps 空调冷冻水系统 由于本工程占地面积大,功能复杂,有连续使用,也有间歇使用,为了达到运行灵活,节能的目的,空调冷冻水系统采用两管制二次泵系统. Chilled water system Due to the large occupied area of this project, the complicated functions and the combination of continuous utilization and intermittent utilization, in order to accomplish the purpose of flexible operation and energy saving, the chilled water system is of two-pipe secondary pump system. 管材: 水管采用焊接钢管及无缝钢管. 本工程的风管除土建风道外,均采用镀锌铁皮咬口制作.每节风管之间用法兰连接. Pipe and duct materials The water pipes adopt welded steel pipes and seamless steel pipes. Air ducts for this project are made of galvanized sheet steel by seaming except ducts by civil construction. Air ducts are connected together by flanges. 一次泵系统: 供应楼冷冻机房 2400kW制冷机配一台离心泵, 流量为412m3/h.配一台备用泵. Primary pump system: Chiller room supply building A centrifugal pump with a flow rate of 412m3/h is provided for 1200kW chiller. One operation pump with a standby corresponds to one chiller. 保温材料: 空调供,回水管,冷凝水管采用酚醛管壳保温. 空调送,回风管以及处理后的新风管采用外贴铝箔的离心玻璃棉板保温. - 管道穿防火墙的空隙处采用岩棉材料等非燃材料填充. Thermal materials phenolic pipes are adopted for thermal insulation of water supply and return pipes for air conditioning, as well as air-conditioning condensate pipes. Aluminum foil faced glass fiber boards are adopted for thermal insulation of air-conditioning air supply and return ducts as well as fresh air ducts after chillers. Non-flammable material will be selected to fill the interspace in the fire protection wall where the ducts go through. 消声与隔振: 冷水机组,水泵等设备采用减振台座,弹簧减振器或橡胶减振垫减振降噪. 在空调机组,新风机组,通风机的进出口采用涂胶帆布软管连接. - 水泵进出水管上采用可曲挠橡胶接头,使设备振动与配管隔离. Noise reduction and vibration isolation Shock absorption bases, spring shock absorbers on rubber shock absorption pads are adopted for equipment, such as water chiller units, pumps, etc to reduce vibration and lower noise. Flexible rubber-coated canvas hoses are adopted far connections of inlets and outlets of air-conditioning units, fresh air handling units and ventilators. Flexible rubber couplings are adopted for the water intake and delivery pipes of the pumps to isolate equipment vibration from their pipes. 空调和通风系统 Air Conditioning and Ventilation Systems 方案设计范围 Scope of schematic design 空调设计 Air Conditioning Design 在体育馆内,一些区域设置空调系统.这些区域划分为: 西侧地下二层的贵宾休息室 东侧地下二层酒店门廊 地下一层的输送区,技术机房,运动员更衣间,医务服务,热身区,裁判区,健身中心,酒店大堂,会议室,厨房,特许区和贵宾大堂混合区. 首层的酒店大堂,酒店区,贵宾门廊,急救 In the stadium, in some ranges air conditioning systems are used. These ranges subdivide themselves as follows: VIP – Lobby in West of levelel -2 Hotel lobby in the east of level –2 Delivary Circle, technical Plantrooms, Changingrooms for the athletes, Medical Service and warm up area, Judges Area, Fitness Center, Hotel Lobby, Conferenz, Kitchen and Concession, Vip lobby- Mixed Zone in level -1 Hotel lobby, Hotel area, Vip lobby, Vip Area, First aid in 0
摘要:近些年来,建筑给排水的最大热点是新型管材的广泛应用。传统的镀锌钢管和普通排水铸铁管由于易锈蚀、自重大、运输施工不便等原因被取而代之。目前, 建筑给排水常用管材主要有塑料管,金属管和复合管三种。现在就常用管材的一些特性,优缺点,使用范围做一简要论述。关键词:建筑给排水 管材 塑料管 金属管 复合管1.塑料管塑料管是合成树脂加添加剂经熔融成型加工而成的制品。添加剂有增塑剂,稳定剂,填充剂,润滑剂,着色剂,紫外线吸收剂,改性剂等。常用塑料管有:硬聚氯乙烯管(PVC-U),高密度聚乙烯管(PE-HD), 交联聚乙烯管(PE-X),无规共聚聚丙烯管(PP-R),聚丁烯管(PB),工程塑料丙烯晴-丁二烯-苯乙烯共聚物(ABS)等。塑料管的原料组成决定了塑料管的特性。塑料管的主要优点:(1).化学稳定性好,不受环境因素和管道内介质组分的影响,耐腐蚀性好。(2).导热系数小,热传导率低,绝热保温,节能效果好。(3).水力性能好,管道内壁光滑,阻力系数小,不易积垢,管内流通面积不随时间发生变化,管道阻塞机率小。(4).相对于金属管材,密度小,材质轻,运输,安装方便,灵活,简捷,维修容易。(5).可自然弯曲或具有冷弯性能,可采用盘管供货方式,减少管接头数量。其主要缺点:(1).力学性能差,抗冲击性不佳,刚性差,平直性也差,因而管卡及吊架设置密度高。(2).阻燃性差,大多数塑料制品可燃,且燃烧时热分解,会释放出有毒气体和烟雾。(3).热膨胀系数大,伸缩补偿必须十分强调。所以,在推广塑料管的同时,还需要发展技术克服其缺点。 塑料管性能 物理性能:塑料管的物理性能和铝塑复合管,钢管,铜管比较见表1:表1物理性能 单位 PVC-U PE PE-X PP PB ABS 钢 铜 密度 g/cm 导热系数 w/mk 50 400 热膨胀系数 mm/m°C 弹性模量 MPa 3000 600 600 210000 110000 拉伸强度 MPa 40 25 >25 28 17 40 700 150 硬度 R 120 70 100 60 230HB 使用温度 °C 0-60 -60-60 -60-95 -20-95 -20-95 -20-80塑料管的物理性能影响管道的方式,用途,补偿措施和管道保温等方面。如:(1).PVC-U、PP、ABS的力学性能相对较高, 被视为“刚性管”,明装较好。反之,PE、PE-X、PB作为“柔性管”适合暗敷。(2).塑料管的使用温度及耐热性能决定了PVC-U,PE,ABS仅能用于冷水管,而PE-X,PP, PB则可作为热水管。当建筑物有热水供应系统且冷热水采用统一管材时耐热性能成为主要指标。(3).塑料管因热膨胀系数高,在塑料管路中尤其是作为热水管,采用柔性接口,伸缩节或各种弯位等热补偿措施较多。其中以PE,PP等聚烯烃类为最。施工安装时如果对此没有足够重视,并采取相应技术措施,极易发生接口处因伸缩节而拉脱的问题。(4).由于导热系数低,塑料管的绝热保温性能优良进而可减少保温层的厚度甚至无需保温。当不同塑料管之间绝热性的比较除导热系数外,还同它们各自的管壁厚度有关。 承压性能:承压性能所涉及的内容是在一定条件下塑料管材能够承受的内压力和恒压下的破坏时间。从而确定与之有关的设计参数以及对管材的质量进行评价和监控。一般进行两项试验:液压试验和长期高温液压试验。 各种管材的承压性能见表2表2管 材 工作压力/MPa 试样试验压力/MPa 接头密封试验/MPa 爆破压力/MPa UPVC 42/h De≤90,4.2PNDe>90,3.36PN PEX ℃常温 ABS 4~8 PB 1.6~2.5/冷水热水 PP-RPP-C 常温℃ 20℃,11h,16MPa80℃,48h,℃,170h, HDPE 热水冷水 卫生性能:理化卫生指标。其中PE,PE-X,PP,PB和ABS易达标。而PVC-U管材在生产时应使用无毒PVC树脂和卫生及稳定剂才能满足卫生性能的要求。 给水塑料管的应用结构形式单一,材料品种众多且性能各异.常用给水塑料管的特点列表如下:表3品种 优 点 缺 点 连接方式 PVC-U 抗腐蚀力强,易于粘合,价廉,质地坚硬 有UPVC单体和添加剂渗出,不适用于热水输送;接头粘合技术要求高,固化时间较长 粘合、螺纹 HDPE 韧性好,较好的疲劳强度,耐温度性能较好;质轻,可挠性和抗冲性能好 熔接需要电力;机械连接,连接件大 挤压夹紧、热熔合、电熔合 PEX 耐温性能好,抗蠕变性能好 只能用金属件连接;不能回收重复利用 挤压夹紧 PB 耐温性能好,良好的抗拉、压强度,耐冲击,低蠕变,高柔韧性 国内还没有PB 树脂原料,依赖进口,价高 挤压夹紧、热熔合、电熔合 PP-R 耐温性好 在同等压力和介质温度的条件下,管壁最厚 热熔合 ABS 强度大,耐冲击 耐紫外线差,粘接固化时间较长 粘合、螺纹、电熔合一般情况聚氯乙烯管由于价格低廉,在不考虑水质影响,在冷水供水系统属于首选管材,而当温度较高时,可选用聚乙烯管或交联聚乙烯管、聚丙烯管、聚丁烯管。 排水塑料管的应用材质单一:硬聚氯乙烯结构形式多样:芯层发泡管,空壁管,螺旋管,芯层发泡螺旋管,空壁螺旋管。其存在的一些问题:(1).热膨胀系数大,需设置伸缩补偿装置来解决。(2).刚度小,平直性差,需加密管卡、支架、吊架来解决。(3).耐热性差,软化温度低,需限制排水温度,限制使用场所和控制与热源的距离来解决。(4).阻燃性差,在穿越楼板、上人屋面的屋面板、防火墙、管道井井壁处需设置阻火圈和防火套管来解决。(5)抗机械冲击性差,需强化施工技术,精心施工来解决。(6)隔声性差,塑料管的噪声大于铸铁管,管道明装且管道位置靠近卧室时,问题尤为突出。降噪的方式,提高管道材质的隔声效果,芯层发泡管空壁管是基于这一思路而开发的;降噪的另一方式是改变水流条件,螺旋管是基于这一思路而开发的。将两种方式结合起来的思路是芯层发泡螺旋管和空壁螺旋管的开发。相同条件下,不同结构形式的排水塑料管,其噪声测定结果:普通管>芯层发泡管>空壁管>螺旋管排水塑料管的应用是在取代普通排水铸铁管的工作上进行的。目前,排水塑料管已可在建筑高度为100m以下的建筑物内使用,但各地区的进展很不平衡。当建筑高度大于、等于100m的高层建筑和不适宜采用排水塑料管的场合,可采用柔性抗震排水铸铁管。[next] 2.金属管 镀锌钢管镀锌钢管的被取代既不意味金属管被取代,也不意味镀锌钢管在整个建筑给水领域被取代。镀锌钢管由于价格低廉、性能优越,防火性能好,使用寿命长等优点,还将在消防给水系统,尤其是自动喷水灭火系统中应用.而塑料管(承压小)则不应在消防给水系统和生活-消防,生产-消防共有系统中应用。 铜管金属管中最具优势的是铜管,铜管应用较久,优点较多,管材和管件齐全,接口方式多样,较多的应用在热水管路中,目前存在的主要问题在于铜的折出量容易超标。 铸铁管给水铸铁管与钢管相比有不易腐蚀、造价低、耐久性好等优点,适合于埋地敷设。缺点是质脆、重量大、长度小等。连接方式一般采用承插连接。卡箍式铸铁排水管是一种新型的建筑用排水管材,60年代开始进入国际市场,经过几十年的推广和应用,这种管材已得到国际上的普遍认可。这种管材与传统的承插式铸铁排水管道相比有许多优点,是一种更新换代产品,但由于这种管材及配件价格相对较贵,所以在国内一直未能得到普及推广。 其它:不锈钢管也受到工程技术人员的青睐,有关方面正从减少壁厚,降低价格方面着手,以利于推广。铝合金管是铝厂向给排水行业推出的新品种。镀镍钢管是和镀锌钢管性质最近,而耐腐蚀性能远远超过镀锌钢管的新颖管材,在解决了降低镀层费用和管材断口处施工现场上镍工艺后,有望在一定范围内得到采用。涂塑钢管则是在金属管材中前景看好的一种管材,且管道布置和敷设、接口方式和施工安装均与镀锌钢管相同,是这种管材最容易被接受。由于其涂层薄、价格低,也最容易被推广。3.复合管:复合管包括衬铅管、衬胶管、玻璃钢管。复合管大多是由工作层(要求耐水腐蚀)、支承层、保护层(要求耐腐蚀)组成。复合管一般以金属作支撑材料,内衬以环氧树脂和水泥为主, 它的特点是重量轻、内壁光滑、阻力小、耐腐性能好;也有以高强软金属作支撑,而非金属管在内外两侧,如铝塑复合管,它的特点是管道内壁不会腐蚀结垢,保证水质;也有金属管在内侧,而非金属管在外侧,如塑覆铜管,这是利用塑料的导热性差起绝热保温和保护作用。根据金属的材料可分为:(1).钢塑复合管(2).不锈钢-塑复合管,塑覆不锈钢管(3).塑覆铜管(4).铝塑复合管,交联铝塑复合管(5)衬塑铝合金管应该说复合管材是管径≥300mm以上给排水管道最理想的管材。它兼有金属管材强度大,刚性好和非金属管材耐腐蚀的优点。但它又是目前发展较缓慢的一种管材。这是因为:(1).两种管材组合在一起比单一管材价格偏高。(2).两种材质热膨胀系数相差较大,如粘合不牢固而环境温度和介质温度变化又较剧烈,容易脱开,而导致质量下降。复合管的连接宜采用冷加工方式,热加工方式容易造成内衬塑料的伸缩、变形乃至熔化。一般有螺纹、卡套、卡箍等连接方式。由于复合管尚属新型管材,我国还未有统一的设计、施工及验收规范。设计及施工人员往往套用镀锌管的工艺来进行设计与施工,故在此不作一一赘述。
要:近些年来,建筑给排水的最大热点是新型管材的广泛应用。传统的镀锌钢管和普通排水铸铁管由于易锈蚀、自重大、运输施工不便等原因被取而代之。目前, 建筑给排水常用管材主要有塑料管,金属管和复合管三种。现在就常用管材的一些特性,优缺点,使用范围做一简要论述。关键词:建筑给排水 管材 塑料管 金属管 复合管1.塑料管塑料管是合成树脂加添加剂经熔融成型加工而成的制品。添加剂有增塑剂,稳定剂,填充剂,润滑剂,着色剂,紫外线吸收剂,改性剂等。常用塑料管有:硬聚氯乙烯管(PVC-U),高密度聚乙烯管(PE-HD), 交联聚乙烯管(PE-X),无规共聚聚丙烯管(PP-R),聚丁烯管(PB),工程塑料丙烯晴-丁二烯-苯乙烯共聚物(ABS)等。塑料管的原料组成决定了塑料管的特性。塑料管的主要优点:(1).化学稳定性好,不受环境因素和管道内介质组分的影响,耐腐蚀性好。(2).导热系数小,热传导率低,绝热保温,节能效果好。(3).水力性能好,管道内壁光滑,阻力系数小,不易积垢,管内流通面积不随时间发生变化,管道阻塞机率小。(4).相对于金属管材,密度小,材质轻,运输,安装方便,灵活,简捷,维修容易。(5).可自然弯曲或具有冷弯性能,可采用盘管供货方式,减少管接头数量。其主要缺点:(1).力学性能差,抗冲击性不佳,刚性差,平直性也差,因而管卡及吊架设置密度高。(2).阻燃性差,大多数塑料制品可燃,且燃烧时热分解,会释放出有毒气体和烟雾。(3).热膨胀系数大,伸缩补偿必须十分强调。所以,在推广塑料管的同时,还需要发展技术克服其缺点。 塑料管性能 物理性能:塑料管的物理性能和铝塑复合管,钢管,铜管比较见表1:表1物理性能 单位 PVC-U PE PE-X PP PB ABS 钢 铜 密度 g/cm 导热系数 w/mk 50 400 热膨胀系数 mm/m°C 弹性模量 MPa 3000 600 600 210000 110000 拉伸强度 MPa 40 25 >25 28 17 40 700 150 硬度 R 120 70 100 60 230HB 使用温度 °C 0-60 -60-60 -60-95 -20-95 -20-95 -20-80塑料管的物理性能影响管道的方式,用途,补偿措施和管道保温等方面。如:(1).PVC-U、PP、ABS的力学性能相对较高, 被视为“刚性管”,明装较好。反之,PE、PE-X、PB作为“柔性管”适合暗敷。(2).塑料管的使用温度及耐热性能决定了PVC-U,PE,ABS仅能用于冷水管,而PE-X,PP, PB则可作为热水管。当建筑物有热水供应系统且冷热水采用统一管材时耐热性能成为主要指标。(3).塑料管因热膨胀系数高,在塑料管路中尤其是作为热水管,采用柔性接口,伸缩节或各种弯位等热补偿措施较多。其中以PE,PP等聚烯烃类为最。施工安装时如果对此没有足够重视,并采取相应技术措施,极易发生接口处因伸缩节而拉脱的问题。(4).由于导热系数低,塑料管的绝热保温性能优良进而可减少保温层的厚度甚至无需保温。当不同塑料管之间绝热性的比较除导热系数外,还同它们各自的管壁厚度有关。 承压性能:承压性能所涉及的内容是在一定条件下塑料管材能够承受的内压力和恒压下的破坏时间。从而确定与之有关的设计参数以及对管材的质量进行评价和监控。一般进行两项试验:液压试验和长期高温液压试验。 各种管材的承压性能见表2表2管 材 工作压力/MPa 试样试验压力/MPa 接头密封试验/MPa 爆破压力/MPa UPVC 42/h De≤90,4.2PNDe>90,3.36PN PEX ℃常温 ABS 4~8 PB 1.6~2.5/冷水热水 PP-RPP-C 常温℃ 20℃,11h,16MPa80℃,48h,℃,170h, HDPE 热水冷水 卫生性能:理化卫生指标。其中PE,PE-X,PP,PB和ABS易达标。而PVC-U管材在生产时应使用无毒PVC树脂和卫生及稳定剂才能满足卫生性能的要求。 给水塑料管的应用结构形式单一,材料品种众多且性能各异.常用给水塑料管的特点列表如下:表3品种 优 点 缺 点 连接方式 PVC-U 抗腐蚀力强,易于粘合,价廉,质地坚硬 有UPVC单体和添加剂渗出,不适用于热水输送;接头粘合技术要求高,固化时间较长 粘合、螺纹 HDPE 韧性好,较好的疲劳强度,耐温度性能较好;质轻,可挠性和抗冲性能好 熔接需要电力;机械连接,连接件大 挤压夹紧、热熔合、电熔合 PEX 耐温性能好,抗蠕变性能好 只能用金属件连接;不能回收重复利用 挤压夹紧 PB 耐温性能好,良好的抗拉、压强度,耐冲击,低蠕变,高柔韧性 国内还没有PB 树脂原料,依赖进口,价高 挤压夹紧、热熔合、电熔合 PP-R 耐温性好 在同等压力和介质温度的条件下,管壁最厚 热熔合 ABS 强度大,耐冲击 耐紫外线差,粘接固化时间较长 粘合、螺纹、电熔合一般情况聚氯乙烯管由于价格低廉,在不考虑水质影响,在冷水供水系统属于首选管材,而当温度较高时,可选用聚乙烯管或交联聚乙烯管、聚丙烯管、聚丁烯管。 排水塑料管的应用材质单一:硬聚氯乙烯结构形式多样:芯层发泡管,空壁管,螺旋管,芯层发泡螺旋管,空壁螺旋管。其存在的一些问题:(1).热膨胀系数大,需设置伸缩补偿装置来解决。(2).刚度小,平直性差,需加密管卡、支架、吊架来解决。(3).耐热性差,软化温度低,需限制排水温度,限制使用场所和控制与热源的距离来解决。(4).阻燃性差,在穿越楼板、上人屋面的屋面板、防火墙、管道井井壁处需设置阻火圈和防火套管来解决。(5)抗机械冲击性差,需强化施工技术,精心施工来解决。(6)隔声性差,塑料管的噪声大于铸铁管,管道明装且管道位置靠近卧室时,问题尤为突出。降噪的方式,提高管道材质的隔声效果,芯层发泡管空壁管是基于这一思路而开发的;降噪的另一方式是改变水流条件,螺旋管是基于这一思路而开发的。将两种方式结合起来的思路是芯层发泡螺旋管和空壁螺旋管的开发。相同条件下,不同结构形式的排水塑料管,其噪声测定结果:普通管>芯层发泡管>空壁管>螺旋管排水塑料管的应用是在取代普通排水铸铁管的工作上进行的。目前,排水塑料管已可在建筑高度为100m以下的建筑物内使用,但各地区的进展很不平衡。当建筑高度大于、等于100m的高层建筑和不适宜采用排水塑料管的场合,可采用柔性抗震排水铸铁管。[next] 2.金属管 镀锌钢管镀锌钢管的被取代既不意味金属管被取代,也不意味镀锌钢管在整个建筑给水领域被取代。镀锌钢管由于价格低廉、性能优越,防火性能好,使用寿命长等优点,还将在消防给水系统,尤其是自动喷水灭火系统中应用.而塑料管(承压小)则不应在消防给水系统和生活-消防,生产-消防共有系统中应用。 铜管金属管中最具优势的是铜管,铜管应用较久,优点较多,管材和管件齐全,接口方式多样,较多的应用在热水管路中,目前存在的主要问题在于铜的折出量容易超标。 铸铁管给水铸铁管与钢管相比有不易腐蚀、造价低、耐久性好等优点,适合于埋地敷设。缺点是质脆、重量大、长度小等。连接方式一般采用承插连接。卡箍式铸铁排水管是一种新型的建筑用排水管材,60年代开始进入国际市场,经过几十年的推广和应用,这种管材已得到国际上的普遍认可。这种管材与传统的承插式铸铁排水管道相比有许多优点,是一种更新换代产品,但由于这种管材及配件价格相对较贵,所以在国内一直未能得到普及推广。 其它:不锈钢管也受到工程技术人员的青睐,有关方面正从减少壁厚,降低价格方面着手,以利于推广。铝合金管是铝厂向给排水行业推出的新品种。镀镍钢管是和镀锌钢管性质最近,而耐腐蚀性能远远超过镀锌钢管的新颖管材,在解决了降低镀层费用和管材断口处施工现场上镍工艺后,有望在一定范围内得到采用。涂塑钢管则是在金属管材中前景看好的一种管材,且管道布置和敷设、接口方式和施工安装均与镀锌钢管相同,是这种管材最容易被接受。由于其涂层薄、价格低,也最容易被推广。3.复合管:复合管包括衬铅管、衬胶管、玻璃钢管。复合管大多是由工作层(要求耐水腐蚀)、支承层、保护层(要求耐腐蚀)组成。复合管一般以金属作支撑材料,内衬以环氧树脂和水泥为主, 它的特点是重量轻、内壁光滑、阻力小、耐腐性能好;也有以高强软金属作支撑,而非金属管在内外两侧,如铝塑复合管,它的特点是管道内壁不会腐蚀结垢,保证水质;也有金属管在内侧,而非金属管在外侧,如塑覆铜管,这是利用塑料的导热性差起绝热保温和保护作用。根据金属的材料可分为:(1).钢塑复合管(2).不锈钢-塑复合管,塑覆不锈钢管(3).塑覆铜管(4).铝塑复合管,交联铝塑复合管(5)衬塑铝合金管应该说复合管材是管径≥300mm以上给排水管道最理想的管材。它兼有金属管材强度大,刚性好和非金属管材耐腐蚀的优点。但它又是目前发展较缓慢的一种管材。这是因为:(1).两种管材组合在一起比单一管材价格偏高。(2).两种材质热膨胀系数相差较大,如粘合不牢固而环境温度和介质温度变化又较剧烈,容易脱开,而导致质量下降。复合管的连接宜采用冷加工方式,热加工方式容易造成内衬塑料的伸缩、变形乃至熔化。一般有螺纹、卡套、卡箍等连接方式。由于复合管尚属新型管材,我国还未有统一的设计、施工及验收规范。设计及施工人员往往套用镀锌管的工艺来进行设计与施工,故在此不作一一赘述。
MECHANICAL PRELIMINARY DESIGN REPORT STADIUM 1.给排水设计 饮用水和污水 Design Water and sewage water .设计基础 - 甲方提供的设计任务书和市政管网综合图 - 建筑专业提供的条件图 - 国家现行的设计规范及有关规定设计简章 .Design bases Design Brief and Municipal integrated network drawing offered by the client. Condition drawings from architectural discipline. Current national design codes and related stipulations 2. 给水系统 通过一根DN200的进水管将水引入.水表安装在进水管上,离红线1米处.供水管在红线内连成环路管网,并接到供应楼的消防水池和给排水水池.由环路管网向必需的室外消火栓和绿化带的喷淋器供水. 2. Water supply system For water supply of this project, DN200 water intake pipes are led in. Water meters are installed on the intake pipes m away from the red line. The water supply pipes are connected into loop networks in the red line and then led to the fire pool and sanitary water pool in the supply buildings respectively. Necessary number of outdoor hydrants and sprinklers for green area will be provided on the loop networks. 设计范围 包括红线内的饮用水,污水,雨水,建筑消防. Design scope Design scope of this project includes water, sewage water, rainwater, fire-protection in the building, and water and sewage water within the red line. 给排水水池与消防水池分开,容量为100m3 .体操馆供水管埋地敷设. Sanitary water pool is separated from fire water pool, volume of sanitary water pool is 100m3. Water supply pipes for the stadium will be laid in the earth. 3.用水量标准 - 体育馆: 15升/顾客·日 K= - 宾馆: 150升/人·日 K= - 餐厅: 50升/顾客·日 K= - 工作人员: 25升/人·日 K= - 地面冲洗用水: 3升/m2日 - 冷却塔补水量:按用水量的2%计 - 未预见水量: 按日用水量20%计 - 消防用水: 消火栓:室内40升/秒,室外30升/秒,火灾延续时间为3小时; 自动喷洒按22升/秒,火灾延续时间为1小时 卷帘水幕用水升/秒·米,火灾延续时间为3小时; Water consumption standard - Stadium: 15L/visitor·day K= - Hotel: 150L/visitor·day K= - Restaurant: 50L/customer·day K= - Staff 25L/person·day K= - Floor cleaning: 3L/m2·day Make-up water for cooling tower: 2% of the actual cold water consumption. Unforeseen water consumption: 20% of the daily water consumption. Water for fire protection Hydrant: 40L/s indoor, 30L/s outdoor, fire duration time is 3h; Sprinkler: 22L/s, fire duration time is 1h; Drencher for rolling shutter: ·m, fire duration time is 3h; 在适当的位置设置饮用水机,在主进口为残障人设置两个饮用水机.为此饮用水系统安装循环泵.机房 设在地下室的水除了机房.当饮用水机不被使用时,应排空,以免水质腐败. 在客房和餐厅内设置电热水器,同时亦为热水供应设置循环泵. 在更衣间旁设置电热水器,为淋浴和洗盥供应热水. 为楼板清洁安装一定数量的水龙头. Some suitable places are supplied with portable water drinking units, two drinking units for disable people are provided at main entrances, for this portable water system, circulating pumps are adopted, the equipment room is located in water treatment center in the basement. When there is no use, portable water will be drained completely to avoid deterioration. Electric water heaters are installed in guest rooms and restaurant, also hot water circulating pumps will be provided for supplying hot water. Electric water heaters are installed near the changing and clothing rooms for supplying hot water for shower and washing. Certain number of water taps are installed for floor-cleaning. 4.用水量 最大日用水量:日 最大时用水量:220m3/时 Water consumption demand Maximum daily water consumption: Maximum hourly water consumption: 220m3/hour 却循环系统 冷却水循环系统采用机械循环系统.总冷却水用量为460m3/h.在供应楼顶设置三台超低噪音冷却塔(230 m3/h, 2x 115 m3/h).进水温度37Co,出水温度32Co .补充水量 9,6 m3/h.补充水由市政供水网直接提供. Cooling water circulation system There are cooling water circulation system in this project, cooling water for the refrigerators adopts mechanical circulation system. Total water consumption of cooling towers is 460m3/h. On roof of the supply building there are 3 ultra-low noise cooling towers (230 m3/h, 2x 115 m3/h), inlet temperature of 37Co, outlet temperature of 32Co, with make-up water of 9,6 m3/h. Make-up water of the cooling towers will be supplied directly by the municipal network. 在消防泵房内有消火栓泵(一个运行,一个备用),喷淋泵(一个运行,一个备用),卷帘雨淋泵(一个运行,一个备用).用于地下车库的泡沫喷淋设备,如报警阀,泡沫压缩罐,化学药剂泵安装在消防设备中心. 消防水箱和消防稳压装置分别安装在车库的四面墙. In the fire water pump room, there are hydrant pumps (one operation, one standby), sprinkler pumps (one operation, one standby) and rolling shutter drencher pumps (one operation, one standby). Fire equipment, which are used for the foam sprinkler system in underground garage, such as fire alarm valves, foam concentrated tank and chemical dosing pump, etc. are provided in fire equipment centers. Four fire water tanks and fire protection stabilized pressure devices are respectively located at four sides next to the garages. 消防用水 消火栓:室内按40升/秒,室外按30升/秒,火灾延续时间按3个小时计 自动喷洒按22升/秒,火灾延续时间按1小时计 卷帘水幕用水量 升/秒·米,火灾延续时间按3个小时计 消火栓:室内,室外用水量皆为756m3; 自动喷洒用水量为 m3; 卷帘水幕用水量为 270m3; 一次火灾用水量为; Water for fire protection Water consumption standard for fire protection Hydrant: 40L/s indoor, 30L/s outdoor, fire duration is 3h Sprinkler: 22L/s, fire duration is 1h Drencher for rolling shutter: ·m, fire duration is 3h Water consumption for fire protection Hydrant: indoor and outdoor water consumptions are 756m3 respectively Sprinkler: m3 Drencher for rolling shutter: 270m3 Water consumption for one fire: m3 消火栓的布置 在整个建筑物内沿墙,沿柱,沿走廊,风塔上及楼梯附近设有必要数量的室内消火栓,消火栓间距小于30米.消火栓管网水平,竖向皆成环状布置,消火栓箱内配有DN65消火栓一支,25米衬胶水龙带一条,φ19毫米喷咀水枪一支,并配消防卷盘(DN25消火栓一支,30米胶管,φ9毫米喷咀水枪一支)且设有可直接启动消火栓泵的按钮;在室内消火栓箱下设有磷酸铵盐手提式灭火器箱.室内消火栓系统在室外设有三组水泵接合器. Hydrant arrangement Necessary number of hydrants are installed indoors along the wall, columns, corridors, and staircases, at intervals of less than 30m. Hydrant networks are connected as a loop both horizontally and vertically. Inside each hydrant box, a DN65 hydrant, a 25m long rubber lined hose, a water nozzle of φ19mm, hose reel (a DN25 hydrant, a 30m long rubber lined hose and a water nozzle ofφ9mm), and a direct starting button for the hydrant pump are provided. Under each indoor hydrant box, a portable ammonium phosphate powder extinguisher box is installed. There are three sets of pump adopters being installed outdoors for the indoor hydrant system. 消防系统 防水泵房及消防水池 供水管DN200在红线内连成环路管网,管网上安装 一定数量的消火栓.两根DN200供水管分别引入供应楼内两个消防泵房内的消防水池.消防水池总容量不应小于4000m3, 每个为. Fire protection system Water pump room and water pool for fire protection The lead-in pipes (DN200) are connected as a loop inside the red line, on the loop, certain number of hydrants are water supply pipes (DN200) are led into the fire water pools at each fire water pump room in supplybuilding. In consideration of the importance of the project, the volume of the fire water pools should be not less than 4000m3, each is . 自动喷淋系统 自动喷淋系统安装在全建筑范围,除了室外和高于10 米的房间.喷淋泵安装在地下的消防泵房内.报警阀设置在地下的消防泵房内和中间的消防设备中心内,水流显示器设在每个防火分区内. Sprinkler system Sprinkler systems will be provided inside the whole building except outside areas and roomshigher than 10m, with sprinkler pumps installed in the underground fire water pump rooms. Alarming valves installed in underground fire water pump rooms and four fire equipment centers in the middle, water flow indicators are installed by fire compartments. 除了安装一个封闭喷淋系统,将为地下车库设置一个泡沫喷淋系统.餐厅内安装93oC启动的自动喷淋头,但在其它房间,仅安装93oC启动的普通和快速反应自动喷淋头.三组泵接合器安装在室外. Besides an enclosed sprinkler system, a foam sprinkler system composed of a proportioning mixer and a foam concentrated tank is provided for the underground garage. Sprinkler actuated at 93oC are provided in the restaurants, but in other rooms, only ordinary sprinklers and fast response sprinklers actuated at 68oC are provided. Three sets of pump adaptors for this system will be installed outdoors. 排水系统 为排水系统设置污水主立管和特别垂直排气管.排气管与污水管在每层连接,污水排出体操馆.餐厅的污水首先在油脂分离池中处理,然后排入室外排水网.给排水污水将被在化粪池收集和处理,然后排入市政排水管网.化粪池在输送区旁.最大天排水量为870m3/天. 9. Drainage system Main vertical sewage pipes and special vertical vent pipes are provided for the drainage system. The vent pipes are connected with sewage pipe at each floor; sewage water is drained out of stadium. Sewage water in the restaurants and garage are treated in the grease and oil separation tank, and then discharged into the outdoor drainage networks. Sanitary sewage water is collected and treated in the septic tank, then drained into the municipal drainage. The septic tanks are located besides the deliverycircle. Maximum daily drainage amount is 870m3/day. 卷帘水幕系统 地下车库设置有卷帘水幕系统.水幕泵安装在消防水泵房内,采用开式雨淋头,电动或手动控制.十组泵接合器安装在室外 Drencher system for rolling shutters Rolling shutter protected by drenchers are provided for the underground garage, the drencher pumps are installed in the fire water pump rooms, open drencher heads are selected, and are controlled both by electrically and manually. Ten pump adapters will be installed outdoors for this system. 地下室内污水设有污水坑,废水设有废水坑,生活污水,废水经潜污泵提升排至室外排水管网,潜污泵的启停皆由磁性浮球控制器的控制. 地下汽车库废水设有废水坑,废水经潜污泵提升排至室外,经隔油池处理后排入室外雨水管网. There are cesspits for sewage water and wastewater pits for wastewater in the basement, the sewage and wastewater is sucked up and drained to the outdoor drainage networks by submerged sewage pumps. Operation of the pumps is controlled by the magnetic floating ball controllers. Wastewater pits are provided for the underground garage, wastewater is sucked up and drained to outdoor oil separation tank by submerged sewage pumps, after treated, wastewater is drained to the outdoors rainwater networks. 在柴油发电机房,变配电房和通讯设备机房设低压二氧化碳气体灭火系统. Low pressure CO2 extinguisher systems are provided in diesel generator rooms, transformer substations and telecommunication equipment rooms. 在本建筑内按"建筑灭火器配置设计规范"在每个消火栓箱下设手提式灭火器箱,箱内设有必要数量的磷酸铵盐手提式灭火器. According to the Code for Design of Extinguisher Disposition in Buildings, portable fire extinguisher box, in which there are necessary number of portable ammonium phosphate powder extinguishers, will be installed under every hydrant box. 在每个消防电梯井底旁设有消防排水坑,废水经潜污泵提升排至室外. Fire water drain pit is provided at side of bottom of each fire elevator well, waste water will be sucked up and drained out by the pumps. 雨水系统 雨水排水屋顶采用压力流排水. 雨水设计重现期按P=10年计算,降雨历时为5分钟,暴雨强度公式按Q=(1+)/(t+)计算. 沿柱在屋面设置雨水沟.雨水通过雨水沟收集,然后进入雨水头和下排管,然后到室外雨水观察井. 10. Rainwater system Pressurized drainage system is adopted for roof rainwater drainage system. Here, return period P=10 years, rainfall duration is 5 minutes, stormwater amount is calculated by the following formula: Q=(1+)/(t+) Rainwater gutters are provided on roof along columns, skylight. Rainwater is collected in the gutter, then to rainwater heads and downpipes, and to the outdoors rainwater inspection wells. 11.管材 - 生活给水管,冷却塔补水管采用铜管,氩弧焊接. - 直饮水管采用不锈管. - 消火栓管,冷却循环管,水幕管,水泵吸水管采用焊接钢管,焊接. - 自动喷洒水管,雨淋水管采用热镀锌钢管,丝扣连接或卡压连接. -二氧化碳管采用无缝钢管焊接. - 地下车库泡沫喷淋水管采用不锈钢管,卡压连接. Pipe material Copper pipes connected by argon arc welding are adopted for the sanitary water pipes, make-up water pipes for cooling towers. Stainless stell pipes are adopted for portable water pipes. Welded steel pipes connected by welding are selected for hydrant pipes, cooling circulating pipes, drencher pipes, pump suction pipes. Hot-galvanized steel pipes connected by threads or compression-seizing are selected for sprinkler and deluge sprinler pipes. Seamless steel pipes connected by welding are selected for CO2 pipes. Stainless steel pipes connected by pressed clamp is selected for the pipes of foam sprinklers in the underground garage. 当雨水两超出雨水沟设计量时,雨水可沿屋檐自由排放.雨水被收集,然后排入市政集水池. When the amount of rainwater is more than the design value of the gutters, water is discharged naturally along the eaves. Rainwater is collected, and then drained to the municipal catch basins. 围绕体育馆的循环池将用于喷洒运动场和作为室外绿化带的储水池. 此池将作为一个循环过滤设施,可容水约 m . 喷洒压力设备和其它必须的过滤设备安装在供应楼里. The circular senic pool surround stadium will be used for spraying sportsfield and as reservoir for outdoor greening. The pool will be used as a circular filtering facility and will be adopted with a water volume of about m . The spray water pressurizing equipment as well as further necessary filtering equipment will be adopted in the supply building. 制冷 Cooling 冷源: 空调冷负荷(估算): 本工程建筑面积共平方米,包括观众区,休息室,更衣室,小会议室,餐厅,办公室和其它附属房.空调设计日峰值冷负荷为,设计日总冷负荷为3 kW. Refrigerating source Cooling load of air conditioning system Total floor area for this building is 50,000sqm, which includes spectator areas, lounges, Clothing and changing rooms small meeting rooms, restaurant, office and other auxiliary rooms. Designed dayly peak cooling load is 2,4MW, designed total dayly cooling load is 3kW. 每台1200kW制冷机配一台 流量为206m3/h离心泵.各配一台备用泵 一次泵采用压差旁路控制. 通过埋地敷管,向游泳体操馆供应冷冻水. A centrifugal pump with a flow rate of 103m3/h is provided for each 1200kW chiller. One operation pump with a standby corresponds to one chiller. Pressure difference branch control is adopted for primary pump Via earth laid pipes from supply building to gymnasium chilled water supply will be deliverded. 冷源的选择: 根据建筑的实际情况,3台制冷机将安装在供应楼内的冷冻机房.设计容量为4800kW. 为了实现能量的效率化使用,设计方案为,1台制冷机的出力为总设计容量的50%.而另2 台.每台出力为总设计容量的25%. 冷冻水系统的主要设备包括3台电动制冷机,一级冷冻泵,二级冷冻泵,自动控制阀等等.冷冻水的供/回水温度为-7/ 12°C. Selection of refrigerating source According to the real condition of the building, 3 chillers are located in the refrigerating plant rooms in the supply building, designed capacity is 2400kW. For actuing in an energy efficient way one chiller about 50% of total capacity ( kW) and two chillers with 25% of total (600 kW each)capacity each are adopted. Main equipment of chilled water system includes 3 electrical chiller, primary cool water pump, secondary chilled water pump and automatic controlled valve, etc. supply/return temperature of the chiller is-7/ 12°C. 二次泵系统:根据使用功能,各制冷机房又分成不同的循环支路. 二次泵采用变频调速控制.根据负荷侧供回水管的压差,控制水泵的转速. 二次泵循环支路的管道采用异程式. Secondary pump system: Each refrigerating plant room is subdivided into different circulation branch loops according to use functions. Variable-frequency speed-regulating control is adopted for secondary pumps. The rotating speed of a water pump is controlled according to the pressure difference between water supply and return pipes. Direct return system is adopted for the pipes of circulating branch of secondary pumps 空调冷冻水系统 由于本工程占地面积大,功能复杂,有连续使用,也有间歇使用,为了达到运行灵活,节能的目的,空调冷冻水系统采用两管制二次泵系统. Chilled water system Due to the large occupied area of this project, the complicated functions and the combination of continuous utilization and intermittent utilization, in order to accomplish the purpose of flexible operation and energy saving, the chilled water system is of two-pipe secondary pump system. 管材: 水管采用焊接钢管及无缝钢管. 本工程的风管除土建风道外,均采用镀锌铁皮咬口制作.每节风管之间用法兰连接. Pipe and duct materials The water pipes adopt welded steel pipes and seamless steel pipes. Air ducts for this project are made of galvanized sheet steel by seaming except ducts by civil construction. Air ducts are connected together by flanges. 一次泵系统: 供应楼冷冻机房 2400kW制冷机配一台离心泵, 流量为412m3/h.配一台备用泵. Primary pump system: Chiller room supply building A centrifugal pump with a flow rate of 412m3/h is provided for 1200kW chiller. One operation pump with a standby corresponds to one chiller. 保温材料: 空调供,回水管,冷凝水管采用酚醛管壳保温. 空调送,回风管以及处理后的新风管采用外贴铝箔的离心玻璃棉板保温. - 管道穿防火墙的空隙处采用岩棉材料等非燃材料填充. Thermal materials phenolic pipes are adopted for thermal insulation of water supply and return pipes for air conditioning, as well as air-conditioning condensate pipes. Aluminum foil faced glass fiber boards are adopted for thermal insulation of air-conditioning air supply and return ducts as well as fresh air ducts after chillers. Non-flammable material will be selected to fill the interspace in the fire protection wall where the ducts go through. 消声与隔振: 冷水机组,水泵等设备采用减振台座,弹簧减振器或橡胶减振垫减振降噪. 在空调机组,新风机组,通风机的进出口采用涂胶帆布软管连接. - 水泵进出水管上采用可曲挠橡胶接头,使设备振动与配管隔离. Noise reduction and vibration isolation Shock absorption bases, spring shock absorbers on rubber shock absorption pads are adopted for equipment, such as water chiller units, pumps, etc to reduce vibration and lower noise. Flexible rubber-coated canvas hoses are adopted far connections of inlets and outlets of air-conditioning units, fresh air handling units and ventilators. Flexible rubber couplings are adopted for the water intake and delivery pipes of the pumps to isolate equipment vibration from their pipes. 空调和通风系统 Air Conditioning and Ventilation Systems 方案设计范围 Scope of schematic design 空调设计 Air Conditioning Design 在体育馆内,一些区域设置空调系统.这些区域划分为: 西侧地下二层的贵宾休息室 东侧地下二层酒店门廊 地下一层的输送区,技术机房,运动员更衣间,医务服务,热身区,裁判区,健身中心,酒店大堂,会议室,厨房,特许区和贵宾大堂混合区. 首层的酒店大堂,酒店区,贵宾门廊,急救 In the stadium, in some ranges air conditioning systems are used. These ranges subdivide themselves as follows: VIP – Lobby in West of levelel -2 Hotel lobby in the east of level –2 Delivary Circle, technical Plantrooms, Changingrooms for the athletes, Medical Service and warm up area, Judges Area, Fitness Center, Hotel Lobby, Conferenz, Kitchen and Concession, Vip lobby- Mixed Zone in level -1 Hotel lobby, Hotel area, Vip lobby, Vip Area, First aid in 0
关于给排水的给排水科学与工程(Water Supply And Drainage)是工科学科中的一种,简称给排水。给排水科学与工程一般指的是城市用水供给系统、排水系统(市政给排水和建筑给排水),好完善的,
2)多年来我国《建筑给水排水设计规范》中的给水设计秒流量计算公式一直沿袭平方根法,计算某些建筑物时计算数值偏大,存在明显缺陷和不足。如我们按照目前美、俄等国在计算给水设计秒流量时采用的概率法计算,又因中国人的生活习惯、饮食结构不同,其计算结果也不合理、不科学。因此,目前国内科研工作者对现行的给水设计秒流量计算公式提出了多种修改、修正式,以弥补原计算公式的欠缺和不足。这些新的修正式,结合实践试算,其结果比原计算公式接近用水的实际工况,宏观上步入了概率的计算方法,但现尚缺乏概率法涉及的计算参数,如高峰期用水定额、高峰期时段历时、用水保证率、传统生活习惯和饮食结构等诸多影响计算式结果的因素,所以采用符合国情的概率法计算给水设计秒流量的工作尚需作大量的调查、统计和科研工作。� 2 开展建筑给水水质保障技术研究� (1)提高了生活饮用水水质标准。随着国家经济实力地增长,卫生部修改了1985年制定的GB5749-85《生活饮用水标准》。修改后标准的相关指标比原水质标准有了较大的提高,如浊度由3 NTU提高到1 NTU;新增了一个对水中总有机物量的限值指标——耗氧量(以CODmn表示),限值为3 mg/L。“标准”提高了,意谓原水处理程度提高、资金投入增加,涉及面较多,需协调处较多。目前,该标准是卫生部发布的。据说,对“标准”规定的水质指标及其带来的各种问题,各部委之间认识还不统一。� (2)为了与各种瓶装商品水,各种功能水区别,同时也从国情出发,建设部制定了CJ94-1999《饮用净水水质标准》行业标准并已于2000年3月1日起实施。一段时期以来,各种水商品充斥市场。喝什么水好,什么水有益于人体健康?众说纷纭,莫衷一是。相信《饮用净水水质标准》的颁布与实施将有利于居高和生活饮用水管道分质供水工程的正常发展。由中国建筑设计院、清华大学等5个单位承担的建设部《建筑及居住小区优质饮用水供应技术》科研课题已经完成,除上述水质标准成果外,在净化工艺及净水机开发、自动控制、系统设计秒流量公式推导及系统设置、管材、管件等方面均取得了突出成果。� (3)国家科委、建设部设立“建筑(居住)区内水质状况调查分析及水质污染途径”的研究课题,并且取得了积极成果。根据污染途径的研究,采用如下防止生活饮用水二次污染的具体措施,是课题成果之一。� ①淘汰钢筋混凝土和钢板水箱。推荐使用FRP水箱、搪瓷钢板水箱、不锈钢水箱及复合钢板水箱。目前市场上又出现自动开闭水箱、充气密闭水箱等新型卫生水箱。� ②为减少二次污染途径,推荐采用变频调速供水系统,取消传统高位水箱。� ③如条件允许,推荐直接从市政干管吸水,采用变频调速供水系统,取消贮水池,不仅充分利用了市政供水压力,还消除了水的二次污染源。� ④推荐选用水质保障设备,如除氟、除铁、除锰设备;推荐选用多种饮用净水设备,如臭氧、活性炭、微滤、超滤纳滤及KDF活性炭、陶瓷过滤等终端处理设备。� ⑤推荐选用多种防二次污染的消毒设备,如臭氧、二氧化氯、次氯酸钠及紫外线等处理设备。� ⑥推荐选用防水质污染的新型给水管道(详见本论文3)、管道附件如倒流防止器等。� 3 积极开展新型管材、管件研究和推广� 建筑住宅内给水管道采用传统的镀锌钢管已有近百年的历史,镀锌钢管对中国自来水行业的发展作出了突出贡献。但随着经济的迅猛发展,人们的生活质量不断提高,对自来水的水质要求也日趋提高。人们对自来水的“红水”、“黑水”等现象反映强烈。导致管网水质恶化的主要原因是建筑物内给水管道的锈蚀严重。冷镀锌钢管一般使用寿命不到la就锈蚀,铁腥味严重。从个别用户水龙头的水样分析化验中得知,细菌总数、大肠菌群严重超标,居民纷纷向政府部门投诉,造成一种社会问题。� 20世纪80年代以前,建筑(住宅)内排水管道主要采用手工砂模承插排水铸铁管,该管材生产方法劳动强度大,生产效率低,产品质量差,影响周边环境质量,也是急待治理的社会问题。 鉴于上述情况,建设部、国家经贸委、国家质量技术监督局和国家化学建材局于1999年12月联合颁布了“建住房〔1999〕295号”文《关于在住宅建设中淘汰落后产品的通知》,文中规定:自2000年6月1日起,在城镇新建住宅中,淘汰砂模铸造排水管用于室内排水管道,推广应用硬聚氯乙烯(PVC-U)塑料排水管和符合《排水用柔性接口铸铁管及管件》(GB/T12772-1999)的柔性接口机制铸铁排水管;禁止使用冷镀锌钢管用于室内给水管道,并根据当地实际情况逐步限时淘汰热浸镀锌钢管,推广应用铝塑复合管、交联聚乙烯(PE-X)管、三型无规共聚聚丙烯(PP-R)管等新型管材。伴随这一政策的出台,市场上也涌现出多种管材,如薄壁铜管、薄壁不锈钢管、PVC-U、CPVC、PE、HDPE、PE-X、PAP、PP-H、PP-B、PP-R、PB、ABS、FRP、各种钢塑复合管及柔性排水铸铁管等。各种管材群雄割据、并驾齐驱。与新型管材配套的管接头,品种繁多、结构和选材各异,各厂家质量参差不齐。各种新型管材和管件虽有良好的发展机遇,但在市场经济条件下,他们能否保持强大的生命力将由建材市场检验。4 积极推广节水节能技术� 水资源匮乏已成为制约我国经济发展的瓶颈。节约能源是我国的国策。在建筑给水排水中,节能节水技术得到了较大的推广与突破。� (1)水资源匮乏地区加强污水资源化和提高水的复用率。中水按回用对象及水质要求,其处理工艺已由传统的二级生化法,发展到三级处理(即增加了过滤和消毒),对要求高的复用水水质,如作为饮用水水源和补充水,可采用高级深度处理工艺,如微滤、反渗透等处理方法;雨水截留、利用技术和建设生态小区,利用湿地处理雨水和生活污水的研究已到工程应用 阶段。� (2)淘汰了升降式铸铁水嘴,推荐采用陶瓷片密封水嘴,推荐公共场所采用感应式或延时自闭式水嘴。� (3)淘汰了9L以上冲洗水箱,推荐采用6L的冲洗水箱。开发了多种节水型卫生洁具和配件,如无冲洗水箱的喷射式便器。� (4)各种高精度的干、湿式水表、IC卡水表、远传水表及用于饮用净水系统,精度达1L/h的远传干式水表等均已问世,且一定要安装分户水表计量考核,既方便了居住区物业管理和居民生活,也杜绝了水资源的浪费。� (5)各种循环冷却水系统的研究成果广泛应用在空调系统中,如射流式冷却塔和喷雾式冷却塔的开发;各种水质稳定剂的研究及系统的智能化控制等也取得较好的进展。� (6)利用海水冲厕。� (7)供水压力应减压至~。� (8)建筑热水系统中对各种热(能)源的开发取得了显著成效。加强余热利用,推荐使用电源。地热和太阳能研究成果已用于工程中。目前,我国已成为全世界太阳能热水器年销售量第一的国家。各种新型间接加热设备已广泛用于集中热水供应系统,如汽——水、水——水换热的浮动盘管式或波节管式半容积和半即热式及板式水加热器及燃油燃气热水机组等。� (9)热水系统水泵、阀门、配套附件等产品开发均取得较大进展,如,平均无故障工作时间达8000h热水泵的问世、各种高灵敏度的温控阀的研制成功等。� (10)从节水、节电、节地角度,开展建筑热水系统模式研究,如干管、支管循环,电伴热热水供应系统研究均取得了一定成果。同时探讨合适的热水供应温度,既能缓解结垢和腐蚀、节能节水,同时又能抑制热水中军团菌等的滋生。 5 建筑给水、建筑热水设备技术热点简介� (1)供水设备:� ①微处理器,实现电机软启动、软制动、节能;� ②变频器自带PLC;� ③直接自市政供水干管吸水、无吸程、无负压、节能;� ④射流泵辅助变频调速供水、节能;� ⑤带有触摸屏的可视化控制;DCS控制系统;� ⑥美观、一体化、、不锈钢化;� ⑦水箱密闭、自动呼吸;� ⑧符合GB/T17219;� ⑨各种优质水处理机组。� (2)热水设备:� ①浮动盘管换热器改进型,如单元组合式、一壳多管式换热器,换热量大,占地面积小; ②波节管、波纹管换热器,传热系数大;� ③当热媒不回收时,直混式换热器,换热效率高;� ④地热技术;� ⑤太阳热水器及其辅助设备;� ⑥管壳式、半即热式、半容积式、容积式及板式换热器共荣共存、分别适应不同工况。 ⑦温度控制阀,精度、价格;� ⑧换热设备的检修、传热元件的振动、磨损脱焊和积垢;� ⑨对半即热式换热器是否设有温度、压力双控制的安全措施。� 6 美化环境、隔振降噪� 治理、保护和美化环境,维持生态平衡是可持续发展的关键。� (1)作为城市景观的重要标志——大型多功能喷泉,如彩色音乐喷泉、激光水幕电影、趣味游戏旱泉等等,在全国各大城市涌现,她集中了水工艺、建筑、动画、声光、机械、自控等多种学科的先进技术。水景喷泉技术的发展对丰富人民文化生活、创造优美生活环境作出了重大贡献。� (2)城市绿地、花园草坪的喷洒工艺出现多种形式喷头,并可通过GPS自动定位和PLC自动控制。� (3)水泵、管道隔振降噪技术已有成熟的工程经验。� (4)为克服塑料排水管噪声大的缺憾,开发出许多新产品,如PE静音排水管、芯层发泡管、螺旋形芯层发泡排水管等,不仅可作单立管排水增大排水流量,同时也可以大幅度降噪。� 7 建筑消防技术方面应用的动态� (1)在消火栓仍作为建筑物消防的主要手段前提下,加强了自动喷淋灭火的力度,为其向消防主体过渡打下了基础。自动喷水灭火系统,是当今世界上公认的最有效的自救灭火设施,是应用最广泛的自动灭火系统。原GBJ84-85《自动喷水灭火系统设计规范》自1985年颁布执行以来,对指导系统的设计,发挥了良好的作用。但随着新技术新情况和新问题不断涌现,公安部会同有关部门修编了该规范,并自2001年7月1日起施行。新规范编号为GB50084-2001。该规范的问世对我国自救式消防技术的充实与完善是一重大进步。� (2)消防泵有了行业标准,规范了消防泵生产。切线泵以其恒压变流量特性引起业内人士极大关注。� (3)《建规》、《高规》、《建筑内部装修设计防火规范》和《人民防空工程设计防火规范》进行了局部修订。为了不断总结经验教训,遏制公众聚集场所,特别是公共娱乐场所和地下商场火灾事故的发生,保护人身财产安全,公安部经商建设部同意对上述四项国家标准进行了局部修订。自2001年5月1日起施行。此次局部修订的条文内容均为强制性条文。� (4)自从国家要求限制和逐步淘汰卤代烷灭火剂、灭火器和灭火系统以来,究竟用哪一种替代物取代卤代烷,至今国家未给出明确技术法规,相关的“气体灭火设计、施工及验收规范”尚未出台。但研究工作,试点工作,在各地方消防部门的积极支持下,已取得了一定的成果,并已应用到工程中。� 8 大屋面雨水排除技术的重大进步� 屋面雨水排除,特别是对大面积车间、厂房屋面雨水排除,经技术经济比较后认为采用内排水时,按传统的重力法计算方法,宜采用单头排水,如采用多斗时,最多不能超过4个。按该计算要求,既使对缺雨的北方大屋面雨水排除,也要有多条雨水悬吊管和立管,除要消耗大量金属管材外,对车间、厂房设备的布置和生产均有较大影响。目前,在中外合资大跨度机库、大剧场、大车间屋面雨水设计中,采用了压力式(虹吸式)雨水斗,采用压力法计算方法,结束了单斗排水或最多4斗排水系统,摒弃了传统的重力法计算方法,使大面积屋面雨水内排水的悬吊管不受雨水斗数量限制,不受坡度限制。压力式(虹吸式)雨水斗的出现和压力法的计算方法的采用,是一重大的技术进步。� 9 积极开展技术和产品的规范、标准、标准图的制定、宣传和执行工作� (1)宣传、学习、贯彻执行有关强制性规范、标准,对工程质量的保障起了重大作用。 (2)《建筑给水排水设计规范》、《游泳池设计规范》、《中水设计规范》、《给水排水制图标准》等国家和行业规范正在修编。� (3)按照“多出、快出、出好”的要求,各种给水排水设备产品的行业标准,如PP-R管、PE管、PAP管、薄壁不锈钢管、径向加筋PVC-U排水管、倒流防止器及地漏等标准及其设计、施工验收规范将陆续颁发执行。� (4)在建设部成立了全国工程建设标准设计领导小组,下设给水排水标准设计委员会、组织编(修)各种国家标准图,提高工程质量和设计效率。 建筑给排水技术是水工业中的一个重要分支,她的发展是与社会进步、国力增强密切相关的。建筑业,尤其是住宅产业的发展,是拉动国民经济新的增长点的支柱产业之一,申奥成功、加入WTO、2008年在北京主办奥运会,为建筑给排水技术的发展提供了绝好的机遇和广阔的市场。我们坚信21世纪是高新科技发展的世纪,是贯彻以人为本、注重环保的世纪,随着国民经济的发展和人民生活水平的提高,建筑给排水技术这支奇葩将会绽放得更加绚丽多彩。
新型排水管材应用研究一、概况 根据建设部《关于发布化学建材技术与产品的公告》精神,应用于排水的新型管材主要是塑料管材,其主要品种包括:聚氯乙烯管(PVC-U)、聚氯乙烯芯层发泡管(PVC-U)、聚氯乙烯双壁波纹管(PVC-U)、玻璃钢夹砂管(RPMP)、塑料螺旋缠绕管(HDPE 、PVC-U)、聚氯乙烯径向加筋管(PVC-U)等。HDPE管由于其特殊的结构与性能,较小的投资,在排水管领域内倍受青睐。因此对新型排水管材的研究以HDPE管为主。 研究的主要内容包括:新型排水管材的内容及分类;物理力学指标;工程应用研究;施工安装、使用与维护管理等。期间进行了资料收集、工艺应用计算及研究、学习参观考察、产品理化性能测试、施工安装、使用与维护管理等研究工作,而且经过努力,顺利地将HDPE管、PVC-U等新型排水管材进行了工程的推广应用,取得了较好的效果,为在q市推广使用新型排水管材开了个好头,赢得了良好的社会效益和环境效益。 二、项目的目的、意义及内容 1.项目的目的、意义 目前,国内排水管材大多数采用钢筋混凝土管,钢筋混凝土管作为排水管使用存在着许多弊端: (1)理化性能不稳定,使用寿命短; (2)综合经济指标高; (3)其生产不符合节能环保政策。 因此,淘汰混凝土管,推广使用塑料管材作为其更新换代产品更加具有重要的意义。高密度聚乙烯中空壁缠绕管(简称HDPE)作为塑料管材中的佼佼者由于其特殊的结构与性能,较小的设备投资,在排水管领域内越来越受到青睐。 目前随着全国各地城市基础建设投资力度的不断加大,新型管道生产企业的不断涌现以及生产能力的不断扩大,必然会在全国掀起“管道革命”的热潮。建设部即将出台政策法规,在全国范围内禁止使用水泥管作为排水、排污管道。因此市场对复合管材的需求将急剧增大。 q市的经济发展水平一直居于省的龙头地位。城市基础建设投资的力度呈加速态势。这为q市的城市建设水平以及新型建材的开发、推广、使用水平提出了更高的要求。因此,开发新型排水管材并尽快地进行推广使用,提高技术及经济性指标,满足可持续发展方针的需要,早日为q乃至全国的城市建设发挥其应有的作用,具有非常重要的意义。 2.研究内容 (1)新型排水管材的内容及分类 (2)物理力学指标 (3)工程应用研究 (4)施工安装、使用与维护管理 三、国内外发展现状 上海市早在1998年以沪建材98第0511号文规定:淘汰水泥管(混凝土管),推广使用塑料管。北京市为迎接2008年奥运会,正准备淘汰水泥排水管,并计划在“十五”期间总投资2800亿元用于市政建设,其中800亿用于市政排水管网建设及污水处理。西方发达国家早在上个世纪八十年代已开发出了替代产品-塑料管材,并极力推广使用。HDPE由于其特殊的中空壁结构,使得管材比重减轻,环刚度增强,而且设备投资也较小,因此在排水管领域内越来越受到青睐。特别是在德国、韩国和日本,大口径排水管中,HDPE缠绕管的使用率分别为60%,75%和90%。韩国政府今年又拨款一兆四千亿韩元,用于HDPE中空壁缠绕管替换水泥管的工程。因此,本课题以HDPE中空壁缠绕管作为研究重点。 四、主要内容 (1)排水管材的分类 市政工程用排水管按其管材特性可分为刚性管和柔性管(塑料管)两大类。 刚性管包括铸铁管、混凝土管、陶制管等,均为传统材料制作的管道,优点是刚性好,环刚度较高,但防腐性能差,用作排污管道需做特殊防腐处理,使用寿命一般为10~20年不等。最大的缺点是易破碎(铸铁管除外),渗漏严重,易造成二次污染。 塑料排水管按其管壁结构可分为实壁塑料管和结构塑料管两大类。实壁管有硬聚氯乙烯管、玻璃钢夹砂管和PE管,结构壁管分为单/双壁波纹管、加筋管和缠绕管三大类。 (2)物理力学指标 管材特性: (1)结构独特,强度高,抗压耐冲击 (2)内壁平滑,摩阻低,过流量大 (3)耐腐蚀,无毒无污染,环保性突出 (4)连接方便,接头密封好,无渗漏 (5)重量轻,施工快捷,降低费用 (6)埋地使用寿命达五十年以上 管材物理性:(见下表)序号 项 目 单 位 性能指标 1 密度 G/cm3 — 2 热膨胀系数 Cm/cm℃ 11×10-5 3 抗拉强度(230) Mpa 21—24 4 弹性模量 Mpa 552—758 5 软化温度 ℃ 126 6 脆化温度 ℃ -70 (3)工程应用研究 用途: HDPE中空壁缠绕管的主要用途可包括: (1)水利工程、自来水工程输水 (2)市政工程雨水、污水排放 (3)工业废水排放、小区排水 (4)盐业输卤、渔业输水 (5)矿井、建筑物内通风系统 (6)电线、电缆护套 我们研究的重点主要是用于市政工程的雨污水排水管。 工程推广与应用 研究伊始,我们便致力于开展HDPE中空壁缠绕管的工程推广与应用的工作,作了大量的调查研究和推广论证工作。一年多来,经过主管部门、业主、设计院和生产厂家的共同努力,我们顺利地将HDPE管、PVC-U等新型排水管材进行了工程的推广应用,在h湾改造工程、砂土路改造工程的k路、a路、t路、g路采用了HDPE管;在砂土路改造工程中的y路、h采用了PVC-U管,都取得了较好的效果,为在q市推广使用新型排水管材开了个好头,赢得了良好的社会效益和环境效益。 (4)施工安装、使用与维护管理 由于HDPE管材本身的特性,以及推广初始阶段不为大多数人所了解,HDPE排水管在施工安装、使用与维护管理的许多方面都与传统管材有较大出入,带来了许多新的问题,同时也给人们对HDPE管材的接受和使用带来了心理疑虑和障碍,主要包括: 1.管道之间的连接,即接口形式; 2.管道与检查井的连接; 3.沟槽开挖与基础处理; 4.回填与管道抗浮; 5.管材环刚度的确定与选用; 6.相关标准与技术规程的不尽完善,等等。 根据我们对HDPE管的研究以及在推广使用过程中的总结,针对以上各方面内容,特提出以下几点: 1. 管道之间的接口形式建议使用密封胶圈柔性接口,不推荐使用热缩套连接。 2.由于材料的收缩率不同,HDPE管道与砖混检查井的连接处易导致渗漏,建议采用防水翼环,防水翼环可与不同管径的HDPE短管连接好后,直接用水泥砂浆浇注成砌块,在砌检查井时可根据流水底高,直接砌入,省时省力。从远期考虑,应注重塑料预制检查井的应用研究与推广。 3.在地下水位较高、流沙等不良地基处施工,应开挖一段、施工一段并迅速回填,注意防止管道的上浮、偏移与下窝,一旦发生,必须返工。 4.目前管道的规格一般仅有4KN/M2、8KN/M2两种,规格系列不够丰富,应进一步细分,以节省成本,提高管材的价格竞争力。 5. 应尽快出台相关的国家标准与技术规程,以利推广。 五、原材料及环境保护 高密度聚乙烯中空壁缠绕管的主要原料是PE(聚乙烯),原料可以全部国产化。 本项目在生产中无废水、废气、烟尘排放,无振动,车间内噪音在80dB以下,厂房外噪音60dB以下,不对环境造成污染。 六、市场预测 城市排水设施是现代化城市不可缺少的重要基础设施,是城市正常运转的必要条件,城市排水设计水平的高低是一个城市现代文明的重要标志。 与发达国家甚至国内先进城市相比,q市的城市排水设施水平较为落后,主要体现在管材的使用上。虽然q市的排水体制是雨污分流制,但在管材的使用尤其是新型管材的使用上,却非常保守。近年来虽然q市排水基础建设项目较多,但所应用的管材却仍多为陶瓷管、混凝土管,鲜见新型管材的工程应用。这与q市飞速发展的经济状况是极不相称的。因此,应借鉴国内外先进城市的做法,逐步淘汰水泥管(混凝土管),大力推广使用新型管材。 根据《国家化学建材产业“十五”计划和2015年发展规划纲要》:塑料管的推广应用主要以UPVC和PE塑料管为主,并大力发展其它新型塑料管。2005年,在全国新建、改建、扩建工程中,建筑排水管道70%采用塑料管,建筑给水和热水供应管道60%采用塑料管,电线护套管80%采用塑料管,建筑雨水排水管道50%采用塑料管城市供水管道(DN400mm以下)50%采用塑料管,村镇供水管道70%采用塑料管,城市排水管道30%采用塑料管,城市燃气管道(中低压管)20%采用塑料管。 根据《q市市政建设“十五”计划及2010年发展规划》:“十五”期间,q市新、翻建市区雨、污水管道的投资为亿元;2006~2010年,将新建、翻建雨、污水管网约100km,投资为亿元。另外随着全国城市排水建设、污水处理及中水回用等投资力度的不断加大,q市本地以及全国市场对新型排水管材的需求将急剧增大,市场前景极为广阔。 七、技术经济比较 中空壁缠绕排水管与与水泥排水管相比较: 具有寿命长、无渗漏、通流量大、施工方便、工种综合费用节省等优势,列表分析如下: 1)以Ф600mm管为例,性能比: Ф600mm中空壁排水管(S≥8KN/m2) Ф600mm水泥管 产品性质 柔性管 刚性管 使用寿命 50年以上 20年 产品价格 490元/m 元/m 工程综合造价 元/m 元/m 结构 受一定外压会弹性变形,但不会破坏 铺土不平造成管子破损 运输施工 重量轻、连接方便、搬运简便,/m 弯曲分歧困难,笨重(260kg/m),施工耗力耗财,费用昂贵 连接方式 收缩模连接,塑料焊接加工连接 凹凸企口结合用水泥 理化性能 耐冲击、耐腐蚀、不漏水,耐寒性高,耐磨性强、寿命长 重量重,耐冲击低,受压易破损、漏水,耐化学性能差 破损率 柔性管,无破损 15% 发展趋势 建设部大力推广使用,市场呈上升趋势 落后淘汰,面临禁止使用 (注:工程综合造价一栏数据由上海市政提供) 八.结论与建议 1.与传统管材相比,新型塑料管材无论从技术性能指标、施工安装工艺还是综合经济比较,都是传统管材所不能比拟的。 2. 在各种新型管材层出的今天,应尽快地出台相应的规章条文,对新型管材进行推广使用,并限制使用传统管材。 3. 尽快地制订各种新型管材的行业规范及施工安装规范,以提高其技术及经济性指标,满足q市可持续发展方针的需要。仅供参考,请自借鉴。希望对您有帮助。
高层建筑给排水工程存在的问题及对策论文
在整个高层建筑中,给排水系统是重要的组成部分,建筑的日常用水都是由给排水系统提供的。在高层建筑施工过程中,给排水系统的安全工程与其他工程是同时进行的,这在一定程度上加大了施工难度,导致在安装过程中出现了许多问题,这在很大程度上影响了建筑的整体质量。对此,必须要采取相应的解决措施,以此确保给排水系统的安装质量。
1 高层建筑给水系统安装存在的问题及解决对策
1. 1 给水系统压力过大的问题及解决对策
在一般情况下,高层建筑采用的是分区竖向供水,但是仍然无法充分保证给水系统的平衡性。如果供水位置过高,设置在屋顶上的水箱高度便无法满足水压要求,水压过低,则会造成冲洗阀不能有效的开启和关闭; 如果供水系统是变频供水,虽然能够保证最高点的水压,但是由于底部的.水压过大,在用水过程中容易出现水花飞溅的现象。针对于上述问题,首先应该进行科学合理的安装设计,在设计过程中应该根据高层建筑的高度及相关要求对给排水系统进行分区,严格禁止将给水系统分开,根据高度可以分成三个给水系统,保证用水的安全性以及舒适性; 其次,在合适的位置设置装减压阀,降低水压,保证卫生器具连接软管的正常使用。
1. 2 水泵安装问题及其解决对策
对于水泵设备的安装,对其精度有着较高的要求,如果施工水平较低,施工工艺粗糙,不仅会导致水泵产生较大的噪声,而且还容易出现漏水的现象。针对于这些问题,首先在选择水泵设备的时候,应该按照国家的标准进行购买; 其次,对水泵配件进行仔细的检查,检查其是否完整、灵活,确认无问题后,才能进行使用。而且在使用之前,应该调试,观察水泵的运行是否正常; 最后,确认水泵机组的长度及型号,审核水泵安装的标高、位置、坡度,在布置机组管线的过程中,按照短、少弯头的要求进行,并正确安装减震位置,保证水泵能够正常安全的运行。
1. 3 设置水池、水箱检修口的问题及其解决对策
在一般情况下,水池检修口应该按照 600mm ×800mm 的要求进行设置,但是这种设置由于结构顶板与水箱之间的距离较短,同时再加上浮球阀与检修口的距离较远,导致检修人员难以对检修口清洗水箱以及抢修浮球阀。针对于上述问题,首先就应该在设计过程中,对检修口的尺寸、位置进行合理的设计; 其次,根据安装设计的要求以及高层建筑的结构确定水箱的尺寸,并定制,保证结构顶板与水池顶入孔之间净空在一米及其以上; 最后,将入孔设置在浮球阀的近端,最佳位置是水池外可以触摸到浮球阀,这样可以为检修提供极大的方便。
1. 4 施工安装阀门的问题及其解决对策
在安装给水系统过程中,一般都会采用多种阀门,用量较大。在施工前应该对阀门的规格、型号进行认真的检查,保证其符合设计要求。同时,检查试验阀门的强度和严密性,避免由于强度不够、严密性差而导致的漏水现象。其相应的解决对策: 首先,根据给水系统的设计要求选择阀门的型号和规格,如果给水管径超过了 50mm 的,应该选择闸阀; 如果给水管径在 50mm 的范围之内,应该使用截止阀,而立管控制阀采用闸阀; 其次,在安装之前,应该对阀门的严密性和强度进行检查;最后,在施工安装过程中,应该严格按照安装说明进行,阀门杆的安装应该超过水平位置,并向上。
1. 5 套管安装的问题及其解决对策
在套管安装过程中,经常出现的问题是固定不够牢固,安装不到位,从而影响了管道的使用时间。针对于这些问题,首先就必须要按照安装标准,楼板内的套管订单应该比装饰地面高出 20mm,比厨卫间的套管顶端低 50mm; 其次,安装钢制套管的时候,应该根据设计,进行加焊固定。
2 高层建筑排水系统的问题及其解决对策
在排水系统中,排水立管在一般情况较长,水流速度快,水量大,因此非常容易导致管道内的气压产生波动,使水与其两相流,从而引起管道堵塞、水封破坏、卫生器具溢水。针对于上述问题,首先应该将排水管设置为乙字管,降低水速,减少水量; 其次,设置专用的通气管,使其与大气相通,保持管内压力接近大气压力。除此之外,专用的通气管还能够在一定程度上降低排水噪声,提高排水能力。针对于排水系统的施工,排水管应该根据设计要求选用,在高层建筑中,一般都会采用柔性抗震铸铁排水管,而支管和立管则采用的是硬聚氯乙烯塑料管。在施工过程中,需要将底层排出管设置在首层地面的位置,预制成整体管段,从预留孔洞中穿入,标高确认准确后,在管道位置进行固定。排出管最好采用两个 45°弯头接出; 而底层排水管及其器具排水支管的安装,需要将底层排水管设置在地下室的地沟内、顶棚下,同时根据室内的地坪线和轴线尺寸等,并按照设计要求,对管路的预留口方向和标高进行检查,如果没有发现问题便可以进行灌水测试。在高层建筑的排水系统中,硬聚录乙烯塑料的使用能解决立管消能问题和防火问题。
除此之外,在施工过程中,还需要注重洞口的封堵工作,以此避免管道出现渗漏的情况。
3 结束语
通过上文的分析可以发现,在高层建筑给排水安装之前,需要对每个施工环节进行合理的设计,严格控制相关的材料质量,做好设计和安装的每个环节,保证安装质量的可靠性,以此满足高层建筑的使用需求。
参考文献
[1]冯霞。 谈高层建筑给排水中常见问题[J]. 山西建筑,2014,18∶ 133- 134.
[2]郑钢。 建筑施工中给排水设计、安装问题[J]. 河南科技,2010,20∶40 - 41.
[3]李跃华。 高层建筑给排水安装施工技术分析[J]. 科技传播,2012,02∶ 77 + 65.
工程建设标准是从事各类工程建设活动的技术依据和准则,是政府主管部门运用技术手段实现对工程建设产品质量控制,推动科技进步和提高建设水平的重要途径。本文针对建筑给排水设计人员在使用标准过程中存在的问题,以及现行国家工程建设标准体系存在的问题展开以下研究:一、对现行标准的定义、特性以及标准之间的层级、逻辑关系进行研究,根据全国标准体系和工程建设标准体系,对建筑给排水技术内涵进行分析,并对建筑给排水设计标准进行整理和划分层次,编制了建筑给排水设计标准体系结构图和标准体系明细表,在此基础上对整个给排水专业的标准进行整理和系统划分,编制了相应的标准体系结构图和标准体系明细表。二、对建筑工程设计文件的设计依据(标准部分)的编制提出一个思路,包括标准的选取和标准的排序,对标准的排序提出“重要程度判别方法”,列举了不同类型工程实例的设计依据的编制,最后总结了公共建筑和住宅设计依据通用版本。三、对我国标准的制定和审查过程进行概述。对现行工程建设标准体系的现状和存在的问题进行分析,并对标准体系的发展方向提出建议;提出建筑给排水设计标准体系在应用中存在的问题并提出相关的优化建议。最后对国际标准化过程中面临的两个问题:专利与标准的问题、标准国际化和技术贸易壁垒的问题进行了分析和探讨。
随着我国现代建筑技术的不断发展,人们对于建筑给排水工程方面也提出了越来越高的的要求。下文是我为大家整理的关于建筑给排水工程论文的范文,欢迎大家阅读参考!
浅谈高层建筑给排水工程设计
摘要:对高层建筑给水系统设计,排水系统设计、室内消防和热水系统设计进行了详细介绍,总结出目前高层建筑给排水存在的问题,并探讨了给排水节水措施,以确保水资源的合理利用。
关键词:建筑给排水;高层建筑;设计;节水措施
1、高层建筑给排水工程设计方法
高层建筑给水排水工程与一般多层建筑和低层建筑给水排水工程相比,基本的理论和计算方法是一致的,但因高层建筑层数多,高度大,结构复杂。近年来建筑给水工程设计方法得到改进。
例:给一个高层建筑为15层的楼房设计给排水:
住宅楼为框架结构,共15层,层高,室外给水管网位于建筑物的北侧,距离外墙为10m,接管点埋深,管径400mm,管材为球墨给水铸铁管,常年提供的水头;室内粪便污水需要经过化粪池处理方可排入市政管网,室外排水管网位于建筑物的南侧,埋深2m,管径600mm,管材为聚乙烯双壁波纹排水塑料管。
设计参数
生活用水定额:qd=150L/(人.d);最大小时生活用水量:Qh=;最高日用水量:Qd=;小时变化系数:kh=;每户人口:m=人;共90户;室内消防用水量:10L/s;消防水箱水量为火灾前10min的水量6m?;贮水池内的消防水量:按火灾延续2h的水量计;雨水重现期:2年。
设计内容
给水系统设计
管道采用钢塑复合管(内衬塑外镀锌)螺纹连接,进行干管安装、立管安装、支管安装,管道安装完毕需进行水压试验,压力设在,并对安装好的管道做好防腐和保温工作,冲洗管道对其进行管道通水试验。
根据《建筑给排水设计手册》上卫生器具的最大静水压力不得超过,因此高层建筑给水系统必须分区。设计任务书给定了市政给水管网提供常年的水压为。根据给水最小所需压力估算方法:第1层,第2层,2层以上增加1层,压力需增加。得的压力能直接供到第6层还多。所以1层~6层为一个区,上面7层~15层为一个区,总共就两个区。1层~6层用市政管网直接供水,其中底层和2层~6层单独设立管。
考虑到此设计对象是15层的高层建筑。市政管网提供的压力不能全部直接供水,所以必须对生活用水进行提升或加压。高层建筑设计一般都使用高位水箱供水,供水压力比较稳定,此设计也使用高位水箱;又因此设计面向高层民用住宅楼,通过查看平面图纸,根据建筑物的布置情况和楼层的承载力情况及水箱本身占用大量的建筑面积,即在楼层中间没有建筑面积可允许安置水箱,串联供水不可实现,因此高区的供水应在地面用泵抽升到高区水箱。
方案(一)与方案(二)相比管材使用量、工程投资相对较少,但它对减压阀的质量要求相对较高,一旦减压阀受损或使用性能降低,低区的静水压力会迅速增加,影响卫生器具的使用。方案(二)采用低区市政管网直接供水,消除了通过依赖减压阀降低静水压力来减少低区供水的现象。基于工程质量和供水水质及水压的可靠性,最终选择方案(二)
排水系统设计
室内排水系统为污水、废水合流系统,地上部分直接排出室外,地下部分分段设置集水坑把地下室污水、废水汇集于坑内,利用潜水泵由集水坑自动控制将其提升至室外。为了保护存水弯水封性能,保持排水系统内的空气压力与大气压取得平衡,使排水管内排水畅通,向排水管内通入新鲜的空气,保持管内的换气,防范因室外管道系统积聚起来的有害气体而伤害到养护人员、引发火灾和腐蚀管道等隐患,还应减少排水系统的噪声,在排水系统中设置通气管。
室内消防工程
室内消火栓给水系统有:分区、不分区两种方式。消火栓的静水压力超过时就需要分区供水,而本设计是15层的小高层,高度不超过50m,静水压力小于,可以不分区。同时本设计的建筑是15层小高层民用住宅楼,造成火灾的隐患少,人员疏散也快,扑救难度不大,高压消防给水无须设置常年的。设置专用的消防泵,从贮水池内抽取消防水,可用生活给水箱在火灾发生初期10min提前给水,并设置止回阀,既消除了消防水箱对楼层负荷,又可减少工程投资。此设计是15层小高层,层高,总楼高不超过45m,根据建筑给排水设计手册!规定消防栓的最大静水压力不超过,此设计无须分区消防供水,可利用消防泵直接供水满足条件。
室内热水工程
应根据建筑物的用途、热源的供给情况、热水用量和卫生器具的布置情况进行技术和经济比较来确定何种热水供应方式。热水供水方式有如下几类。按供应范围不同有:集中供热、局部供热、区域供热。
2、目前建筑给排水存在的问题
控制超压出流产生的水量浪费
生活给水系统按规定竖向分区后仍然存在着部分卫生器具配水点水压偏大的问题,而这是常常被忽视的。卫生器具的额定流量少于单位时间内的出水量,影响给水系统正常分配水的流量。如不采取减压节流措施,将造成水资源浪费、水压过高、漏水量增加等弊病,同时易产生水击、噪声和振动,致使管件损坏和破裂。这些水量的浪费不容忽视。
管道和阀门的损坏
我们可看到的路边给水管道在管子接缝处及法兰、阀门连接处向外冒水,而我们看不见的地下更不知有多少漏水处。管道受损及腐蚀,阀门不严等问题导致大量水流失。
热水系统浪费水量巨大
建筑热水供应已成为建筑给水的重要部分,由于设计不当,其浪费已非常严重,造成一定损失。所以给水系统供水应保证冷热水压力均衡,采用循环系统以确保每户开龙头就有热水,降低水量浪费。
3、我国建筑给排水节水措施
提高用水效率
1)严格执行生活用水量定额标准,饮用水、生活用水、景观用水、绿化用水按各个水质要求分别供给。
2)采用节水系统,如节水的卫生器具,利用限制卫生器具的流出水头、红外线感应龙头和便器等。
3)选择一个可再生能源,如风能、太阳能、水能、海洋能、地热能、生物能等非化石能源用于建筑的热水供应。对于不同的场合采用不同的热源形式。
雨水的利用
利用雨水收集系统再循环得到符合标准的水质进行绿化浇灌,处理后的雨水还可用于冲洗厕所,这不仅可减少用水量还可减轻污染。提高地基的保水能力,合理规划雨水流经途径,引入雨水沉淀池再利用。
污水排放和二次利用
建筑中水系统是典型的资源可持续利用装置,将建筑物产生的污水、废水加以收集并对其处理,在节省资源和保护环境的基础上对生活污水和废水的重复利用。
节水指标
节水指标有三类:
1)雨洪水利用率:常年降雨量除以使用或收集量;
2)水使用率:正常使用量除以使用量;
3)循环量:一次性用量乘以循环次数。
4、结语
在给排水设计时,我们应正确合理的选择系统和方案,以达到节水节能的目的,确保水资源的合理利用。
参考文献:
[1]孙志魁.我国绿色建筑给排水节能新技术的应用新探.中国新技术新产品,2012(1):45.
[2]杨天峰,张旺.低碳经济下建筑给排水的节能问题研究.科技创业月刊,2010,23(9):161-162.
[3]赵培林.浅议绿色建筑住宅的节水设计.机电产品开发与创新,2009,22(3):40-41.
[4]李倩.绿色建筑给排水设计的节水途径探析.企业导报,2012(1):273.
浅析建筑工程给排水施工技术
摘要:本文作者结合实际工作经验,对建筑工程的给排水施工技术进行了分析,提出了自己的见解。
关键词:建筑工程;给排水;施工技术
随着我国现代建筑技术的不断发展,人们对于建筑给排水工程方面也提出了越来越高的的要求。在设计和施工时要不断积累经验,深入分析各种常见问题,促进给排水施工技术的发展。
1 建筑给水方面的管道施工
给水管道材料的种类和选用
现在在新型建筑中用的较多的给水管材主要包括:聚丙烯类、聚乙烯类、聚丁烯类、工程塑料类,以及还有一些复合管类,例如:钢塑管、铝塑管、铜塑复合管等。虽然可供选择的材料有许多种,但在每一个具体施工工程中也必须根据实际情况进行选择。而且在管材的选用上还受到许多因素的影响,必须对国家政策、施工标准、地区特点、工程性质以及施工标准等因素进行综合考虑,选择最优管材。其中还要特别注意的是,管道的使用位置以及其使用方法是在管材选用时需要着重考虑的,还有就是管件与连接也是选取管材时容易忽视的一个关键的问题。
给水管道的施工
在对给水管做热熔连接时,必须要掌握好加热的时间和连接将要插入的深度。如果加热时间过长就使水管融化,如果加热时间过短也不能更好连接;如果插的过深,就会造成管道断面减少;如果插的过浅也会使降低接口处强度。所以,加热时的温度、加热时间和接缝压力是影响热熔连接质量的三个关键因素。
2 建筑排水管道常见问题的原因分析
排水管道方面经常出现的问题是漏水、堵塞问题。出现这些问题的原因也比较多,第一,就是施工中出现的问题,大多是施工单位没有选择合格的管材,为了一时经济利益以次充好,或者是在安装前没有进行漏水实验,也或是一些不合格的材料运用到工程中导致漏水现象的发生;比如说管道穿墙(楼板)设置套管的缺陷与不足较为普遍。有的虽然加了套管,穿越楼板与楼板面齐平或嵌入楼板有的穿越墙面,比饰面多出20-50mm,有的没有设套管或预埋套管偏位,于脆用水泥圈(楼面)塑料圈(墙面)护(粘)住,掩人耳目,有的套管比管道只大一个规格,有的大三至五个规格,套管与管道间隙有的用泡沫、油麻堵塞等等套管的设置应按(GB50242-2002)规范第规定.“安装在楼板内的套管,其顶部应高出装饰地面20mm,安装在卫生间及厨房内的套管,其顶部应高出装饰地面50mm,底部应与楼板底面相平,安装在墙壁内的套管其两端与饰面相平。穿过楼板的套管与管道之间缝隙应用阻燃密实材料和防水油膏填实。端面光滑。穿墙套管与管道之间缝隙宜用阻燃密实材料填实,且端面应光滑。管道的接口不得设在套管内”。第二,就是设计方面出现了问题,导致管道安装好以后容易堵塞;第三,就是住户使用时出现了问题。
3 建筑给排水施工的特点
管道安装具有的特点
在这几年里,给水管道的材料大多使用的是PP-R管和UPVC管。因为这两种管道具有轻便、耐高压、抗腐蚀、质量安全、使用卫生、通水阻力小、使用寿命较长的特性,所以安装中最明显的特点就是便于安装。对于PP-R管的安装来说,连接前要清除管道上附着的灰尘后,在按照严格的施工流程来进行安装,但是其中需要注意的是在在对管道进行热熔是一定不能旋转,以免加热过度,而且在管道连通后还要采取一定措施对其进行冷却。对于UPVC管的安装来说,安装时一定要使用排水胶粘结。在涂完胶以后还要注意的就是胶干时间,具体的时间应依据当地气候和温度的变化来进行调节,还要注意不能沾水。如果是在环境温差较大的地方安装,必须使用管道伸缩节。
给排水管道的试压
当所有管道安装完成之后,还要对所有部位进行全面的检测,主要包括检测已安装的管道和阀门等设备是否符合设计和技术要求规定,如果有问题应立即拆除予以更换或是维修。检测的具体方法是用临时的短管来替代安装的管道,把所有的开口处封闭,从管道最低处开始灌水,在最高处进行放气。如果出现异样,要及时停止检测,并立即排水。在试压完成后,还对所有管道要进行吹洗。
4 提高建筑的给排水施工技术的具体措施
随着建筑技术的发展,生产工艺的不断改进和提高,对给排水工程的设计、施工、维修和运行管理的要求也就越来越高。要想使管网达到优质、高效、低能耗运行的目的,除要有合理的设计方案外,给排水系统安装质量的优劣将会对日后的使用产生极大的影响。
管道施工的措施
对于管道的施工来说主要是注意加热时间、加热温度、接缝压力这三个方面的问题,施工中运用最多的是钢塑复合管,在对其施工中应采用螺纹连接的方法,插入管道的长度应严格按照标准旋转深度进行控制;在对管端和管螺纹进行加工后,还要进行密封处理,这时需要使用聚四氟乙烯生料带来进行缠绕螺纹;施工中需要选用厌氧密封胶密封过的管道接头,必须在养护24h之后再进行试压。施工中要用专门的施工机具,不能随便更该。
W型铸铁管的施工方法
有关W型铸铁管的具体施工措施,第一步就是下料,在切割管材时要选用专门的切割工具,主要是保证管口的平直。第二步是连接,进行连接时先要松开卡箍,再取出内衬中的橡胶圈,把箍套和橡胶圈放在入管口的一侧,使管口对齐后,随后把橡胶圈放在接口上,最后锁紧了箍套紧固了螺丝就算完成了管道连接。第三步低支架的设置,对于一般的管材安装来说,如果每隔3m设置一个支架其实是可以的,但是对于W型无承口机制排水铸铁管接口来说就不行了,因为其属于柔性接口,当支架放在管道中间时,理论上可以将管道保持平衡,可是在实际工作中,找到重心点是很难的,所以经常无法保证管道接口的平滑,如果采用每隔设置一个支架的方法来进行布置,这样就可以很好地解决管道外观和管道坡度的问题。
建筑给排水施工的监管
给排水管道的设计与施工是一项很复杂的措施,其中关于管道的铺设和管道的安装都容易出现问题,所以有关管道施工的监督也是一项非常重要的方面。因为管道施工工期较长设计建筑工程的的许多阶段,所以监管也可以分为多个阶段来进行。
首先,在工程施工前期阶段的监管,在施工前就应该仔细阅读施工图纸,充分了解设计者的设计意图和目的,这样才能保证施工过程中不偏离设计图纸的要求,也不能在施工中随意变更设计方案。
其次,是在基础主体结构施工阶段的监管,在基础主体施工中,要注意排水系统的排水管和给水管的引入管在穿越建筑物或地下构筑物外墙处时,是否按设计要求预留好了足够的孔洞以及设置好的套管。
再次,就是装修阶段的监管,在装修施工阶段主要是对给排水管道系统安装阶段,主要是注意装修工程不能破坏原有的管道路线的设置或是预留管道的破坏,必须在明确所有管道布置之后再结合装修方案进行施工。
5 结束语
随着我国建筑技术的不断发展,对给排水工程的设计、施工和运行管理等方面的要求也越来越高。优质的安装施工质量和科学的管理是保障管网系统高效安全运行的必要条件。为了满足给排水建筑施工技术要求,提高施工质量,需要施工人员不断学习,提高自身的技术素质,只有这样,才能保证安装工程的质量,立足于建筑安装工程的基本建设。
参考文献:
[1] 王胜飞;民用建筑给排水工程施工质量常见问题及预防措施[J].中小企业管理与科技(下旬刊),2010,(08).
[2] 金生;建筑工程给排水施工常见问题解决措施探讨[J].现代商贸工业,2011,(09).
[3] 刘康;建筑工程给排水施工常见问题及解决措施研究[J].科技致富向导,2011,(01).
[4] 何新辉,魏晓斌.高层建筑给排水设计分析研究[J].中国房地产业,2011,(04).
[5] 李霞,高层建筑给水排水工程课程教学实践与探讨[J].山西建筑,2011,(01).